Vdo Inputs - THOMSON MEC 310#GENSET CONTROLLER Installation And Operation Manual

Genset controller
Hide thumbs Also See for MEC 310#GENSET CONTROLLER:
Table of Contents

Advertisement

4220 VDO fuel level input 1.1
No.
Setting
4221
Fuel level 1.1 (P3)
4222
Fuel level 1.1 (P3)
4223
Fuel level 1.1
4224
Fuel level 1.1
4225
Fuel level 1.1
4226
Fuel level 1.1
4230 VDO fuel level input 1.2
No.
Setting
4231
Fuel level 1.2 (P3)
4232
Fuel level 1.2 (P3)
4233
Fuel level 1.2
4234
Fuel level 1.2
4235
Fuel level 1.2
4236
Fuel level 1.2
4310 VDO oil press. input 2.1
No.
Setting (D)
4311
VDO 2.1
4312
VDO 2.1
4313
VDO 2.1
4314
VDO 2.1
4315
VDO 2.1
4316
VDO 2.1
4320 VDO oil press. input 2.2
No.
Setting (D)
4321
VDO 2.2
4322
VDO 2.2
4323
VDO 2.2
4324
VDO 2.2
4325
VDO 2.2
4326
VDO 2.2
4460 VDO water temp. input 3.1
No.
Setting
4461
VDO 3.1
4462
VDO 3.1
4463
VDO 3.1
4464
VDO 3.1
4465
VDO 3.1
4466
VDO 3.1
PM075 REV 2 09/08/20
MEC 310 GENSET CONTROLLER

VDO inputs

Set point
Delay
Output A
Output B
Enable
Fail class
Set point
Delay
Output A
Output B
Enable
Fail class
Set point
Delay
Output A
Output B
Enable
Fail class
Set point
Delay
Output A
Output B
Enable
Fail class
Set point
Delay
Output A
Output B
Enable
Fail class
Page 98
Min. setting
Max. setting
0%
100%
0.0 s
100.0 s
R0 (none)
R26 (relay 26)
R0 (none)
R26 (relay 26)
OFF
ON
See description of fail classes
Min. setting
Max. setting
0%
100%
0.0 s
100.0 s
R0 (none)
R26 (relay 26)
R0 (none)
R26 (relay 26)
OFF
ON
See description of fail classes
Min. setting
Max. setting
0.0 bar
10.0 bar
0.0 s
100.0 s
R0 (none)
R26 (relay 26)
R0 (none)
R26 (relay 26)
OFF
ON
See description of fail classes
Min. setting
Max. setting
0.0 bar
10.0 bar
0.0 s
100.0 s
R0 (none)
R26 (relay 26)
R0 (none)
R26 (relay 26)
OFF
ON
See description of fail classes
Min. setting
Max. setting
0° C
150° C
0.0 s
100.0 s
R0 (none)
R26 (relay 26)
R0 (none)
R26 (relay 26)
OFF
ON
See description of fail classes
Factory
setting
10%
5.0 s
R0 (none)
R0 (none)
OFF
Factory
setting
99%
5.0 s
R0 (none)
R0 (none)
OFF
Factory
setting
4.0 bar
5.0 s
R0 (none)
R0 (none)
OFF
Factory
setting
4.0 bar
5.0 s
R0 (none)
R0 (none)
OFF
Factory
setting
95° C
5.0 s
R0 (none)
R0 (none)
OFF