Wiring; Important Information - Pilz PSEN sl2-IL1-P Operating Manual

Table of Contents

Advertisement

Wiring

5
Wiring
5.1

Important information

}
Information given in the
}
The power supply must meet the regulations for extra low voltages with protective elec-
trical separation (SELV, PELV).
}
The power supply must have an overvoltage protection of ≤ 35 V DC.
}
Make sure you comply with the wiring technology requirements (DIN EN 60204-1) and
manipulation protection requirements (EN ISO 14119).
}
Inrush current based on the cable length (see
}
The protection type (see
tion cables are used - these are available as an accessory - and when the connector
torque is complied with (see Technical details).
}
All the signals are based on the ground connection A2.
}
Use only the cables listed in the
}
Make sure that the sealing areas on the connector and the socket of the connection lines
are not damaged.
Operating Manual PSEN sl2-IL1/2/3-P
1005909-EN-02
Technical details [
Technical details [
WARNING!
In the event of a power failure guard locking of the safety gate is not
guaranteed
In the event of a power failure, guard locking cannot generate force and
guard locking of the safety gate is not guaranteed. This can lead to serious
injury or death.
– Ensure that the risk assessment takes a power failure into account.
Order reference Accessories [
52]
must be followed.
Maximum inrush current [
52]) is only achieved when Pilz connec-
63]
60]).