Function description
Input 31/Y1
}
When the signal at the input 31/Y1 changes from low to high (control command of the
magnetic guard locking) and the actuator is detected (safety gate closed) this is pro-
cessed as an activation request of the guard locking.
}
The safety outputs 12 and 22 switch independently of the guard locking.
}
If there is a low signal at the input 31/Y1, the guard locking is deactivated.
}
If you are using the SDD the input 31/Y1 cannot be used for the activation request of the
guard locking. The input 31/Y1 is only used as an input for SDD.
}
The guard locking is activated again when the signal switches from high to low and then
again to high at the input 31/Y1.
Magnetic guard locking device and magnet monitoring
}
The locking magnet is switched on if
– a high signal is present at the input 31/Y1 and
– the actuator is detected (safety gate closed) and
– when no SDD is used.
}
The holding force of the locking magnet is tested on power-up.
}
After a signal change at the input 31/Y1 to low, wait for at least 500 ms, before supplying
a high signal again at the input 31/Y1 again. The max. switching frequency (see
nical details [
}
If the safety gate is in a locked condition and is opened by force, the safety outputs will
shut down.
}
Guard locking may only be deactivated by the higher level safety controller when the haz-
ardous machine movement has been completed.
}
Detection of guard locking errors
– If the holding force is not reached (due to soiling, for example) the holding force is not
– When the locking magnet is switched on and an open winding or short circuit winding
– When the locking magnet is switched on and a magnet operation or monitoring fault is
Operating Manual PSEN sl2-IL1/2/3-P
1005909-EN-02
52]) must not be exceeded.
confirmed due to the monitoring of the locking magnet and a warning is displayed
(see
Normal operation [
tion.
is detected, the safety switch switches to the fault condition.
detected, the safety switch switches to the fault condition.
41]). The safety switch does not switch to the fault condi-