Replace drain plug.
Remove lid assembly.
Remove sleeve.
Clean
Dose with MC1+ Protector
O ring
The lid seal should be cleaned and checked for
wear when servicing MagnaClean. It is Best
Practice to replace the lid and drain valve seals
at each service.
"Only use Silicon grease or water to lubricate
O ring.
Do not use flux or EP grease."
Turn locking pin 90° and remove.
CAUTION: Ensure valves are off
Disconnect.
Remove.
CAUTION: Clean and inspect collets and
lubricate seals with water only.
Fit quick release trigger and canister onto
valves.
CAUTION: Ensure canister is firmly pushed onto
valves until fully engaged.
Replace locking pin and turn 90° to lock
Helyezze vissza a leürítő dugaszt.
Távolítsa el a fedélszerkezetet.
Távolítsa el a tokot.
Tisztítsa meg
Nedvesítse MC1+ Protectorral
O-gyűrű
A MagnaClean szervizelésekor a fedél tömítését
ki kell tisztítani, és ellenőrizni kell, hogy nem
használódott-e el. A bevált gyakorlat szerint
minden egyes szerviznél ajánlott kicserélni a a
fedél és a leürítő szelepek tömítését.
"Csak szillikonzsírt vagy vízt használjon az
O-gyűrű lubrikálásához.
Ne használjon fluxot vagy EP zsírt."
Fordítsa el 90°-kal a rögzítő tüskét, és távolítsa
el.
FIGYELEM: győződjön meg arról, hogy a
szelepek ki vannak kapcsolva
Kapcsolja szét.
Távolítsa el.
FIGYELEM: tisztítsa és vizsgálja meg a gyűrűket
és a tömítéseket csak vízzel lubrikálja.
Szerelje fel a gyorskioldó kapcsolót és a patront
a szelepekre.
FIGYELEM: A patront erősen nyomja a
szelepekhez, amíg teljesen a helyére nem kerül.
Helyezze vissza a rögzítő tüskét és a záráshoz
fordítsa el 90°-kal
29

Advertisement

loading
Need help?

Need help?

Do you have a question about the MagnaClean Micro2 and is the answer not in the manual?

Subscribe to Our Youtube Channel