Replace drain plug.
Remove lid assembly.
Remove sleeve.
Clean
Dose with MC1+ Protector
O ring
The lid seal should be cleaned and checked for
wear when servicing MagnaClean. It is Best
Practice to replace the lid and drain valve seals
at each service.
"Only use Silicon grease or water to lubricate
O ring.
Do not use flux or EP grease."
Turn locking pin 90° and remove.
CAUTION: Ensure valves are off
Disconnect.
Remove.
CAUTION: Clean and inspect collets and
lubricate seals with water only.
Fit quick release trigger and canister onto
valves.
CAUTION: Ensure canister is firmly pushed onto
valves until fully engaged.
Replace locking pin and turn 90° to lock
"Vervang de aftapstop."
Verwijder de deksel.
Verwijder de huls.
Reinigen
Doseren met MC1+ Protector
O-ring
De dekselafdichting moet worden gereinigd en
op slijtage worden gecontroleerd tijdens het
onderhoud van MagnaClean. Het is de beste
werkwijze om de deksel- en aftapstopafdichting
bij elk onderhoud te vervangen.
"Gebruik alleen siliconenvet of water om de
O-ring te smeren.
Gebruik geen vloeimiddel of EP-vet."
Draai de borgpen 90° en verwijder deze.
ATTENTIE: De kleppen moeten dicht zijn
Ontkoppelen.
Verwijderen.
ATTENTIE: Reinig en inspecteer behuizingen en
smeer afdichtingen alleen met water.
Plaats de snelsluiter en de bus op de kleppen.
ATTENTIE: Zorg dat de bus stevig op de kleppen
wordt gedrukt tot deze volledig vastzit.
Breng de borgpen aan en draai deze 90° om te
vergrendelen