Page 1
Advanced Central Heating System Flushing User Guide for Combination and Sealed Systems...
Page 2
Monitor the MagnaCleanse system throughout operation. Check jubilee clips are secure before and during operation For the most up to date version of the MagnaCleanse User Guide visit adey. com. Warranty Terms & Conditions can be found at adey.com Clean...
Page 3
You will also need MagnaClean domestic filter To achieve the best protection for the boiler, it is important that the flushing process is carried out with the MagnaCleanse hose-to-valve connector attached to the return pipe of the system. For maximum effect it is recommended that cleaner is added for a minimum of 1 hour: MC3+ - Leave for up to 28 days.
Page 4
Ensure drain valve is in lower hose. N.B. The flow through MagnaCleanse RapidFlush filter should enter the bottom right and exit top left. Turn OFF isolation valves on the RapidFlush filter.
Page 5
SDS drill, set to hammer only mode with no rotary action, agitate open radiator for 15-20 seconds, along the bottom of the radiator. Repeat process on each radiator, moving from furthest away radiator to radiator closest to the boiler. Remember to monitor the MagnaCleanse throughout operation.
Page 6
Sludge removal tool available at adeyspares.co.uk. Set the boiler control to OFF. Attach a drain hose to the MagnaCleanse drain valve and secure with jubilee clip. Turn OFF the HTV connector isolation valve 2 on the return pipe to the boiler, leaving the HTV isolation valve 1 open.
Page 7
Open any bypass valves previously closed. Commission the system following the manufacturer’s instructions. Before leaving the property, carry out the final job – service MagnaClean filter ensuring a final check is carried out for leaks. Remember to monitor the MagnaCleanse throughout operation.