Difl-Ctf-A_Det_T; Difl-Ctf-B_Det_T; Difl-Ctf-C_Det_T - Toshiba GR200 Series Instruction Manual

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Data ID
2.2.7
Signal monitoring point
DIFL (Function ID: 410001)
Element ID
Name
8300011BB0
ADD.DIFLFS
8000001C20
DIFL-A
8000001B65
DIFL-ARC-BLOCK
8100001C21
DIFL-B
8200001C22
DIFL-C
8000021C20
DIFL-CTF-A
8100021C21
DIFL-CTF-B
8200021C22
DIFL-CTF-C
8000021B64
DIFL-CTF_ALARM
8100021BB0
DIFL-CTF_BLOCK
8300021B63
DIFL-CTF_DET
8000021B60
DIFL-CTF_DET-A
8100021B61
DIFL-CTF_DET-B
8200021B62
DIFL-CTF_DET-C
8300021B23
DIFL-CTF_DETECT
8000021B65
DIFL-CTF_DETECT-A
8100021B66
DIFL-CTF_DETECT-B
8200021B67
DIFL-CTF_DETECT-C
8300031B23
DIFL-IDSV
8000031B60
DIFL-IDSV-A
8100031B61
DIFL-IDSV-B
8200031B62
DIFL-IDSV-C
8300001B64
DIFL-OPT
8000001B61
DIFL-OPT-A
8100001B62
DIFL-OPT-B
8200001B63
DIFL-OPT-C
8000001B60
DIFL-OR
8200001BB1
DIFL-RDIF_BLOCK
8100001B66
DIFL-STUB-COND
8000031C20
DIFL-SV-A
8100031C21
DIFL-SV-B
8200031C22
DIFL-SV-C
8300031BB0
DIFL-SV_BLOCK
8000001BB0
DIFL-TP_BLOCK
8000001B20
DIFL-TRIP-A
8100001B21
DIFL-TRIP-B
8200001B22
DIFL-TRIP-C
8F00011B23
DIFLFS_OP
8100001BB4
DIFL_3PTP
8200001BB5
DIFL_ARCBLOCK
8F00001BB2
DIFL_BLOCK
8000001BB3
DIFL_INST_OP
8400021BB1
EXTERNAL_DIFL-CTF
Description
Add File-safe condition
DIFL relay element operated (phase-A)
Autoreclose block signal by DIF-L protection operation
DIFL relay element operated (phase-B)
DIFL relay element operated (phase-C)
DIFL-CTF relay element operated (phase-A)
DIFL-CTF relay element operated (phase-B)
DIFL-CTF relay element operated (phase-C)
Alarm signal by CT failure detection
DIF-L ctf detect block
CT failure detection
CT failure detection (phase-A)
CT failure detection (phase-B)
CT failure detection (phase-C)
CT failure detection
CT failure detection (phase-A)
CT failure detection (phase-B)
CT failure detection (phase-C)
Differential current monitoring
Differential current monitoring (phase-A)
Differential current monitoring (phase-B)
Differential current monitoring (phase-C)
DIF-L protection operated
DIF-L protection operated (phase-A)
DIF-L protection operated (phase-B)
DIF-L protection operated (phase-C)
DIFL relay element operated (3-phases OR)
Remote differential detect block
DIF-L STUB condition
DIFL-SV relay element operated (phase-A)
DIFL-SV relay element operated (phase-B)
DIFL-SV relay element operated (phase-C)
Differential current monitoring block
DIF-L trip block
Trip signal by DIF-L protection operation (phase-A)
Trip signal by DIF-L protection operation (phase-B)
Trip signal by DIF-L protection operation (phase-C)
Fail safe for DIF-L trip
Trip signal by DIF-L protection operation (3-phase)
Autoreclose block signal by DIF-L protection operation
Block all the above four
DIF-L protection instant operation command
External CTF condition
- 39 -