Toshiba GR200 Series Instruction Manual page 92

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

DIFL#1
DIFL#2§
From PROT-COMM
DS_OPEN
DIFL-STUB-Test†
DIFL-STUB
Figure 2.6-11 STUB logic furnished in the local IED
†Note: For testing the stub protection, set On for scheme switch [DIFL-STUB-Test];
consequently, the user can examine the function regardless of the DS condition.
‡Note: The trip circuit (TRC) is discussed separately. See Chapter
circuit
§Note: The DIFL#2 element is only available in the [TERM_TOPOLOGY]=2Term-Dual.
DIFL operation at terminal-H
(ii)
On the other hand, the current data received from the opposite terminal is set to be zero when
the opposite terminal does not operate. That is, the IED_H gets to sense the operation of the
terminal G; the operation of the opposite can be sensed by using open terminal detection
function†. Consequently, the DIFL function does not need to have a respace for a fault such
that it is illustrated Figure 2.6-12.
CT1
G
CB(Closed)
Fault
CB(Closed)
CT2
G
Line
CB(Closed)
Terminal-G
Figure 2.6-12 Fault occurred beyond Stub zone
†Note: On should be set for the [OTD] for the operation. For more information, see the
Chapter
A
≥1
≥1
B
≥1
C
≥1
A
B
C
≥1
&
8100001B66
On
On
. Note that the trip signal generated opens the three-poles.
DS
IED_G
Current
data
Relay application: Communication application
- 69 -
8000001B67
&
8100001B68
8200001B69
Line GH
IED_H
6F2S1914 (0.49)
To TRC‡
DIFL-TRIP_A
DIFL-TRIP_B
DIFL-TRIP_C
DIFL-STUB-COND
Relay application: Trip
CT1
H
CB(Closed)
CB(Closed)
CT2
H
Line
CB(Closed)
Terminal-H
.
GRL200 (Soft 033 & 037)
8300001B64

Advertisement

Table of Contents
loading

Table of Contents