Cold-Starting The Ups Using Batteries - Huawei UPS2000-A-6KTTL User Manual

Table of Contents

Advertisement

UPS2000-A-(6 kVA-10 kVA)
User Manual (App)
Shutdown Method
Method 2: Choose Config > Control >
Power-on/off on the app to shut down
the inverter. After successful shutdown,
the UPS enters bypass mode. For
details about how to install and log in
to the app, see "Installing the App"
and "Logging In to the App."
Method 3: On the WebUI, choose
Monitoring > UPS System > Running
Control to shut down the UPS.
----End
Shutting Down the Inverter to Transfer the UPS to the No Output State
Step 1 Shut down loads.
Step 2 Select one method from
Step 3 Switch off the external battery circuit breaker (if any) or disconnect battery cables.
Step 4 Switch off the mains AC input circuit breaker K1 and output circuit breaker Q1 of
the UPS. After all indicators turn off and fans stop, the UPS shuts down, and the
loads are powered off.
----End

5.7 Cold-Starting the UPS Using Batteries

Cold-Starting the UPS Using Batteries
Step 1 Switch on the external battery circuit breaker (if any) or connect battery cables.
Step 2 Hold down the UPS button for 3s (the bypass indicator, battery indicator, and
inverter indicator are on at the same time), and the UPS is powered on. After the
UPS initialization is complete (about 10s), the indicator status changes and the
UPS enters the standby state (the WiFi indicator is on and the fault indicator
blinks). Hold down the UPS button for more than 5s, and the UPS enters battery
mode.
Issue 02 (2024-01-30)
NO TE
For details about how to shut down the UPS on the WebUI, see the
User Manual .
Copyright © Huawei Digital Power Technologies Co., Ltd.
Icon
Table 5-3
to shut down the inverter.
5 Power-On Commissioning