Huawei UPS2000-A-6KTTL User Manual page 72

Table of Contents

Advertisement

UPS2000-A-(6 kVA-10 kVA)
User Manual (App)
No.
3
4
5
6
7
8
Issue 02 (2024-01-30)
Item
Cable connections for USB
ports and network ports
Labels
Ground cable connections
Distances between cable ties
Operating environment
Cable short circuits
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation and Cable Connection
Expected Result
Cables to USB ports and network ports
are connected correctly and securely.
Labels are neatly attached to both
ends of each cable, and the
information on the labels is concise
and understandable.
The UPS ground cable is securely
connected to the ground bar in the
equipment room. Check that the
resistance between the UPS ground
cable and the equipment room ground
bar is less than 0.1 ohm using a
multimeter.
Distances between cable ties are the
same, and no burr exists.
Conductive dust and other foreign
matter are cleaned up from the device
service.
Check that cables are open-circuited
using a multimeter or an insulation
resistance tester.
65