UPS2000-A-(6 kVA-10 kVA)
User Manual (App)
The following table lists the backup time upon factory delivery, which decreases as the battery
capacity decreases. The table is for reference only.
Table A-1 Backup time parameters for the battery pack ESS-240V12-7AhBPVBA04
(6 kVA UPS; calculated based on 90% battery efficiency)
Load (%)
100
80
50
30
Table A-2 Backup time parameters for the battery pack ESS-240V12-9AhBPVBA04
(6 kVA UPS; calculated based on 90% battery efficiency)
Load (%)
100
80
50
30
Issue 02 (2024-01-30)
A
NO TE
Load (W)
5400
4320
2700
1620
Load (W)
5400
4320
2700
1620
Copyright © Huawei Digital Power Technologies Co., Ltd.
Battery Backup Time
One
Two
Battery
Battery
Pack
Packs
(min)
(min)
5
16
8
22
16
38
33
71
One
Two
Battery
Battery
Pack
Packs
(min)
(min)
8
20
10
32
21
48
40
95
A Battery Backup Time
Three
Four
Battery
Battery
Packs
Packs
(min)
(min)
30
38
39
53
64
91
121
180
Three
Four
Battery
Battery
Packs
Packs
(min)
(min)
36
46
48
64
85
121
160
226
91