UPS2000-A-(6 kVA-10 kVA)
User Manual (App)
Startup Method
Method 3: On the WebUI, choose
Monitoring > UPS > Running Control
to start the UPS.
----End
5.5 Powering On Loads
Procedure
Step 1 When the UPS runs properly, switch on the UPS AC output circuit breaker Q1 to
supply power to loads.
----End
5.6 Shutting Down the UPS
Shutting Down the Inverter to Transfer the UPS to Bypass Mode
Step 1 Shut down the inverter to transfer the UPS to bypass mode using one of the
following methods.
Table 5-3 Shutdown methods
Shutdown Method
Method 1: Hold down the button on
the UPS panel for more than 5s.
Release the button when the inverter
indicator blinks and you hear a beep
sound. Do not press any button during
inverter shutdown. When the
shutdown command is successfully
delivered, and the inverter indicator is
off, the UPS shuts down the inverter
output and enters bypass mode.
Issue 02 (2024-01-30)
NO TE
For details about how to start the UPS on the WebUI, see the
Manual .
NO TE
To prevent triggering overload protection, start the loads with higher power and then loads
with lower power.