UPS2000-A-(6 kVA-10 kVA)
User Manual (App)
Issue 02 (2024-01-30)
Figure 5-13 Quick Settings
Table 5-1 Quick Settings
Item
Description
Voltage
Specifies the system output
level(V)
voltage level. This
parameter is configurable
only after the inverter is
shut down.
Frequency
Specifies the system output
level(Hz)
frequency level. This
parameter is configurable
only after the inverter is
shut down.
System time
Synchronizes the system
time to the UPS.
Battery type
Specifies the type of
batteries connected to the
UPS.
Single
Specifies the voltage of
battery
each battery in a battery
voltage (V)
string connected in series.
Set this parameter based
on the actual configuration.
This parameter is
configurable in non-
battery mode.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Power-On Commissioning
Setting
Value Range
Set as
220, 230, and
required.
240. The
default value
is 220.
Set as
50, 60, and
required.
automatic.
The default
value is 50.
-
-
VRLA batt.
VRLA batt.
(default
value)
Set as
2, 6, and 12.
required.
The default
value is 0.
73