Capacity Test - Huawei UPS2000-A-6KTTL User Manual

Table of Contents

Advertisement

UPS2000-A-(6 kVA-10 kVA)
User Manual (App)
Figure B-1 Adjusting the shallow discharge ratio
Discharge ratio: indicates the percentage of discharge capacity to the total
dischargeable capacity. The parameter can be set to a value between 10% and
50%, and the default value is 20%. The parameter is configurable in any mode.
Step 2 On the app, choose Configuration > Control.
Step 3 Set the Shallow discharge test after all conditions are met. Tap the Shallow
discharge test, the test starts after about 5s.
Step 4 Tap Stop test to forcibly stop the battery shallow discharge test.
----End
B.2 Capacity Test
Context
Before a capacity test, ensure that:
● The UPS works in normal mode, and the battery SOC has reached 100% for
● No high temperature, charger fault, or discharger fault has occurred.
● The load rate ranges from 5% to 100%, and the load fluctuation is less than
Procedure
Step 1 On the app, choose Config > Control.
Step 2 Set the Capacity test after all conditions are met. Tap Capacity test and the test
starts after about 5s.
Issue 02 (2024-01-30)
NO TICE
two hours.
10%.
Copyright © Huawei Digital Power Technologies Co., Ltd.
B Testing Batteries
94