Annual Maintenance - Huawei UPS2000-A-6KTTL User Manual

Table of Contents

Advertisement

UPS2000-A-(6 kVA-10 kVA)
User Manual (App)

6.2.3 Annual Maintenance

Table 6-6 Annual maintenance checklist
Item
Capacity
test
(recomme
nded)
Battery
connectio
n
Issue 02 (2024-01-30)
Expected Result
When the UPS is
backed up,
discharge a battery
to the undervoltage
alarm threshold to
refresh the capacity
of the battery.
1. When battery
strings are
powered off,
check the
reliability of each
connection point
from positive
terminals to
negative
terminals. All
points must be
connected
reliably.
2. Use a torque
wrench to check
the tightening
torque for each
battery screw.
The torque must
meet the
requirements of
the battery
manufacturer.
After checking
that the battery
screws meet the
requirements,
mark the screws
for later check.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Troubleshooting
1. Locate the fault cause.
2. If the fault persists,
contact technical
support.
1. Rectify any abnormal
connection.
2. If the fault persists,
contact technical
support.
6 Maintenance
Maintenance
Interval
Annually
Annually
85