Huawei UPS2000-A-6KTTL User Manual page 49

Table of Contents

Advertisement

UPS2000-A-(6 kVA-10 kVA)
User Manual (App)
Item
Input voltage
range
Rated frequency
Frequency range
Input power factor
Generator input
capacity
Table 2-16 Bypass input electrical specifications
Item
Power system
Input voltage
Voltage range
Rated frequency
Frequency range
Input system
Table 2-17 Output electrical specifications
Item
Power system
Rated output
voltage
Output power
factor
Issue 02 (2024-01-30)
6 kVA
Phase voltage: 80 V AC to
280 V AC (When the
ambient temperature ranges
from 0°C to 40°C, the load is
linearly derated from 100%
to 40% when the voltage
ranges from 80 V AC to 176
V AC.)
50 Hz/60 Hz
40–70 Hz
≥ 0.99 (100% resistive load)
Minimum: 1.35 times of the UPS rated capacity
Specifications
Single-phase, three-wire
220 V AC/230 V AC/240 V AC
● Upper threshold: 10%, 15%, 20%, or 25% at 220 V AC
● Upper threshold: 10%, 15%, or 20% at 230 V AC
● Upper threshold: 10% or 15% at 240 V AC
● Lower threshold: 10%, 20%, 30%, 40%, 50%, or 60%
50 Hz/60 Hz
50/60±6 Hz (adjustable with a tolerance of 0.5–6 Hz, ±2 Hz
by default)
Supports only one power source.
Specifications
Single-phase, three-wire
220 V AC/230 V AC/240 V AC
0.9
Copyright © Huawei Digital Power Technologies Co., Ltd.
2 Product Description
10 kVA
Phase voltage: 80 V AC to
280 V AC (When the
ambient temperature
ranges from 0°C to 40°C,
the load is linearly derated
from 100% to 40% when
the voltage ranges from 80
V AC to 176 V AC.)
42