Troubleshooting by Remote Controller
2.24 Actuation of Low Pressure Sensor
E4
Remote
Controller
Display
Applicable
RZR, RZQ
Models
Method of Error
Abnormality is detected by the pressure value with the low pressure sensor.
Detection
Error Decision
Error is generated when the low pressure is dropped during compressor operating.
Conditions
Operating pressure: 10 psi
Abnormal drop of low pressure (Lower than 10 psi)
Supposed
Defective low pressure sensor
Causes
Defective outdoor unit PCB
Stop valve is not opened.
Clogged filter
Service Diagnosis
SiUS281117
133