2-3. Single UPS mounting

Installation and wiring must be done in accordance with local electrical laws and regulations by trained
professionals.
Ensure that electrical wiring and building breakers are in line with the capacity of the UPS to
1)
prevent electric shock or fire risk.
NOTE: Do not use a wall outlet as an input power source for the UPS, as the current value is less than
the maximum input current of the UPS. The container can be damaged and destroyed.
2) Turn off the electrical switch in the building before installation.
3) Turn off all connected devices before connecting to the UPS.
4) Prepare cables based on the following table:
Type
INSPIRE 83330-QS
INSPIRE 83340-QS
NOTE 1: The cable for INSPIRE 83340-QS must be able to withstand currents in excess of 80A. It is
recommended to use AWG 6 or thicker cables for Phase and AWG 4 or thicker cables for Neutral for
safety and efficiency.
NOTE 2: The selection of cable colors must be followed by local electrical laws and regulations.
5) Remove the terminal block cover on the back panel of the UPS. Then connect the cable according to
The following terminal block diagram: (Connect the ground/earthing cable first when making
other cable connections. Unplug the last ground/earth cable when connecting the UPS!)
NOTE: For dual input models with a single input power system, connect the input terminals to
AC power source and connect input and bypass input at the same time (show dotted line
on the wiring diagram below).
Terminal block wiring diagram for INSPIRE 83330-QS & INSPIRE 83340-QS
Input(Ph)
Output(Ph)
8
6
TO UPS BAT+
PBAT
TO UPS BAT N
NBAT
TO UPS BAT-
Battery cable connection scheme
5
Wiring spec (AWG)
Neutral
8
4
6
4
Battery
Ground
4
4
4
4