3) Turn off the output breaker and disconnect the parallel cable and share the UPS current cable you
want to remove. Now, you can disconnect the UPS from the parallel system.
4) Turn on the input breaker of the remaining UPS and the system will switch to Bypass mode. Set the
maintenance switch from "BPS" to "UPS position and reinstall the maintenance bypass cover.
5) Turn on the rest of the UPS according to the previous section.
Warning: (Only for parallel systems )
Before turning on the parallel system to activate the inverter, make sure that all the maintenance
switches of the unit are in the same position.
When the parallel system is turned on, please do not operate any unit maintenance switch.
Parallel systems do NOT support ECO mode. Therefore, please DO NOT "Enable" ECO mode in any
unit.

3-6. Error Codes

Error
codes
01
Bus start failure
02
Bus ends
03
Bus below
04
Unbalanced buses
06
Overcurrent converter
11
Inverter soft start failure
12
High inverter voltage
1 3
Low voltage inverter
Inverter output L1 (channel to
14
neutral) short-circuited
Inverter output L2 (channel to
15
neutral) short-circuited
Inverter output L3 (channel to
16
neutral) short-circuited
Inverter output L1-L2 (line to
17
line) short-circuited
Inverter output L2-L3 (line to
18
line) short-circuited
Inverter output L3-L1 (line to
19
line) short-circuited
Negative power interference
1A
Inverter L1
L2 inverter negative power
1B
interference
L3 inverter negative power
1C
fault
21
Short circuit SCR battery
23
Open circuit inverter relay
25
Line cable errors
Parallel communication
31
failure
41
Over temperature
42
DSP communication failure
43
Overload
45
Charger error
Error events
Error codes
46
Incorrect UPS settings
47
MCU communication failure
49
Phase errors at input and output
61
Bypass SCR short circuit
62
Pass the SCR open circuit
63
Abnormal voltage waveform at L1 phase
64
Abnormal voltage waveform at L2 phase
65
Abnormal voltage waveform at L3 phase
67
Short circuit O/P bypass
68
Pass the O/P line to the short circuit line
69
Short circuit SCR inverter
6C
BUS voltage drops too fast
6D
Current sampling error value
6E
SPS power fault
6F
Reverse battery polarity
71
PFC IGBT overcurrent in L1 phase
72
PFC IGBT overcurrent in L2 phase
73
PFC IGBT overcurrent in L3 phase
74
INV IGBT overcurrent in L1 phase
75
INV IGBT overcurrent in L2 phase
76
INV IGBT overcurrent in L3 phase
77
ISO Over temperature error
78
LCD & MCU communication failure
79
EEPROM error