Danfoss ECL Comfort User Manual page 58

Hide thumbs Also See for ECL Comfort:
Table of Contents

Advertisement

32j
Service parameter(s) 63-64
63 Time constant, compensation temperature
Circuit
I
Controls how fast the compensation temperature (S1) influences
the desired balance / flow temperature.
OFF: The desired balance / flow temperature will
1:
50:
64 Compensation temperature, 2. point
Circuit
I
When the temperature measured by S1 falls either below or gets
higher than the set value, the controller changes the desired
balance / flow temperature.
The influence on the desired balance / flow temperature is set in
lines 65, 66 and 63.
Set the temperature.
The compensation temperature could typically be the outdoor
temperature.
The settings in lines 60-66 can be used to change the desired
balance / flow temperature in relation to for example the outdoor
temperature .
The grey
side of the
ECL Card
Setting range
OFF / 1 ... 50
not be adjusted any further.
The desired balance / flow temperature will
be adjusted quickly.
The desired balance / flow temperature will
be adjusted slowly.
Setting range
-20 ... 110 °C
Factory setting
OFF
Factory setting
5 °C