Page 7
Relay Outputs EKE 1B has 1 relay output: • Type SPDT relay. Digital Output can be used to connect either a solenoid valve or an alarm. • The relays cannot be used for the direct connection of capacitive loads such as LEDs and ON/OFF control of EC motors.
Page 8
• The stepper motor is connected to the “Stepper Valve” terminals (see terminal assignment) with a standard M12 connection cable. • To configure stepper motor valves other than Danfoss stepper motor valves, the correct valve parameters must be set as described in the Valve configuration section (see manual for details).
• Steady green = valve fully open • Both green and red flashing = valve-related alarm USER INTERFACE EKE 1B can be setup using one of the following user interfaces: 1. Danfoss KoolProg software 2. Danfoss MMIGRS2 external display 3. Communication bus: Modbus RS485 RTU KoolProg KoolProg is a software tool for quickly and easily configuring EKE controllers.
Page 10
Connecting external MMIGRS2 display CAN RJ CAN RJ MMIGRS2 display can be used to set up EKE 1B. The display can be used not only for setting up the necessary param- eters, but also as an external display during operation to MMIGRS2 show important parameters, e.g.
Setup wizard via MMIGRS2 display When all connections to the controller have been made, after the power is switched on, the Danfoss logo will appear for 5 seconds, then the Home screen will be displayed. To access the Wizard: press and hold enter to access the Login screen, the commissioning password is 300, scroll down the Setup and service menu and select “Setup wizard”.
Page 12
The setting will depend on the system requirement. Parameter: R012 Main Switch Select valve type Select predefined Danfoss valve type ETS, ETS C, KVS, KVS C, CCM, CCMT, CTR, or user defined. Parameter: I067 Valve configuration Application mode...
Page 13
EKE 1B – Commonly used parameter identification PNU - equivalent to the Modbus register no. (Modbus address +1). Actual value are read/written as 16-bit integer values without decimals. This is the default value as read via Modbus. Parameter Default Description...