10e
10.3
Ventilation system with constant
room temperature control
Control principle:
PI control of the inlet temperature (S3) and P control of
the room temperature (S2). The adjusted temperature is
controlled by the motorized valve M1 in the primary circuit of
the air heater. Fan P1 is controlled by relay R1, damper P2 by
relay 2.
System settings
Circuit Line Description
I
C
I
85
I
87
Balance temperature
Application selection
R2 relay cut-in delay
Recomm.
setting
23 °C
0
180 sec.