Danfoss ECL Comfort User Manual page 17

Hide thumbs Also See for ECL Comfort:
Table of Contents

Advertisement

Connections of controlled components
Establish these jumpers:
1-5-8-10-12 and
jumper from 2 to common N-terminal
Terminal
Description
1 (L)
Voltage supply 230 V a.c.
2 (N)
Voltage supply 230 V a.c.
3 M1
Actuator - open
4 M1
Actuator - close
5
230 V a.c. voltage supply for
actuator M1
6 M2
Actuator - open, damper
7 M2
Actuator - close, damper
8
230 V a.c. voltage supply for
actuator M2
9 P1
Fan
10
230 V a.c. voltage supply for
fan P1
11 P2
Damper
12
230 V a.c. voltage supply for
damper P2
Temperature sensor connections, see section 14a.
10l
Max. load
0.2 A / 230 V a.c.
0.2 A / 230 V a.c.
0.2 A / 230 V a.c.
0.2 A / 230 V a.c.
4 (2) A / 230 V a.c.
4 (2) A / 230 V a.c.

Advertisement