32d
Service parameter(s) 35
35 Limitation temperature influence, max.
Circuit
I
Set the influence from the limitation temperature on the desired
balance / flow temperature.
Set the influence of the max. limitation
temperature (set in line 30).
Influence higher than 0:
The desired flow temperature / balance
temperature is increased, when the limitation
temperature gets higher than the set limit.
Influence lower than 0:
The desired flow temperature / balance
temperature is decreased, when the limitation
temperature gets higher than the set limit.
Influence
0
Example
The limitation temperature is set to 50 °C.
The influence is set to -2.0.
The actual limitation temperature is 2 degrees too high.
Result:
The desired flow temperature / balance temperature is changed
by -2.0 x 2 = -4 degrees.
The grey
side of the
ECL Card
Setting range
-9.9 ... 0 ... 9.9
Max. limitation > 0
Limit
Max. limitation < 0
Factory setting
-4.0