Danfoss ECL Comfort User Manual page 63

Hide thumbs Also See for ECL Comfort:
Table of Contents

Advertisement

Service parameter(s) 85-88
85 Application type selection
Circuit
I
Choose whether the controller should operate as heating
controller, cooling controller or as a combined heating and
cooling controller.
Choose application.
0:
1:
2:
86 Relay R1 cut-in delay time
Circuit
I
Set the delay time for activating relay R1.
Set the delay in seconds.
87 Relay R2 cut-in delay time
Circuit
I
Set the delay time for activating relay R2.
Set the delay in seconds.
88 Output status, relay R1
Circuit
I
Set the actual output status for the relay when the control mode
is one of the following: Comfort, setback or frost protection.
Setting
The need for frost protection occurs when sensor
S6 registers frost temperature (line 143).
Setting range
Heating application (examples are shown in
section 10.1, 10.2 and 10.3).
Cooling application (examples are shown in
section 10.7 and 10.8).
2-stage heating, heating and cooling
application (examples are shown in section
10.4, 10.5 and 10.6).
Setting range
0 ... 899 sec.
Setting range
0 ... 899 sec.
Setting range
Comfort
mode
0
Closed
1
Closed
2
Open
3
Open
0 ... 2
0 ... 3
Reduced
mode
Open
Open
Closed
Closed
32o
Factory setting
0
Factory setting
180 sec.
Factory setting
0 sec.
Factory setting
1
Frost
protection
Closed
Open
Closed
Open
The grey
side of the
ECL Card