Danfoss ECL Comfort User Manual page 19

Hide thumbs Also See for ECL Comfort:
Table of Contents

Advertisement

Connections of controlled components
Establish these jumpers:
1-8-10 and
jumper from 2 to common N-terminal
Terminal
Description
1 (L)
Voltage supply 230 V a.c.
2 (N)
Voltage supply 230 V a.c.
6 M2
Actuator - open, damper
7 M2
Actuator - close, damper
8
230 V a.c. voltage supply for
actuator M2
9 P1
Circulation pump
10
230 V a.c. voltage supply for
circulation pump P1
Temperature sensor connections, see section 14a.
10n
Max. load
0.2 A / 230 V a.c.
0.2 A / 230 V a.c.
4 (2) A / 230 V a.c.