Danfoss ECL Comfort User Manual page 54

Hide thumbs Also See for ECL Comfort:
Table of Contents

Advertisement

32f
Service parameter(s) 37-42
37 Time constant for temperature limitation
Circuit
I
Controls how fast the actual limitation temperature adapts to the
desired limitation temperature.
Adjust the time constant for the temperature
limitation. The setting will eliminate the difference
between the acceptable and the actual limitation
temperature.
The difference is integrated to adjust the desired
flow temperature / balance temperature.
OFF: The desired flow temperature / balance
1:
50:
42 Time control of relay R2
Circuit
I
The setting determines whether R2 should follow the schedule in
circuit I or II.
1:
2:
The grey
side of the
ECL Card
Setting range
OFF / 1 ... 50
temperature will not be adjusted any
further.
The desired flow temperature / balance
temperature will be adjusted quickly.
The desired flow temperature / balance
temperature will be adjusted slowly.
Setting range
Relay R2 will follow the schedule of circuit I,
the setting in line 89 and R1.
Relay R2 will follow the schedule of circuit II
and the setting in line 89.
Factory setting
Factory setting
1 / 2
OFF
1