KEB COMBIVERT F5 Instruction Manual page 32

Hide thumbs Also See for COMBIVERT F5:
Table of Contents

Advertisement

Display Plaintext COMBIVIS
E.OL2
ERROR overload 2
GB
E.OS
ERROR over speed
E.PFC
ERROR Power factor control
E.PrF
ERROR prot. rot. for.
GB
E.Prr
ERROR prot. rot. rev.
E. Pu
ERROR power unit
E.Puci
ERROR pow. unit code inv.
E.Puch ERROR power unit changed
E.PUCO ERROR power unit commun.
E.PUIN ERROR power unit invalid
E.SbuS ERROR bus synchron
E.SEt
ERROR set
E.SLF
ERROR! Software limit switch forward
E.SLr
ERROR software limit switch reverse
GB- 32
Value Meaning
19
Occurs if the standstill constant current is exceeded (see
technical data and overload characteristics). The error can
only be reset if the cooling time has elapsed and E.nOL2 is
displayed. E. OP
DC-link circuit too high.
Occurs if the DC-link circuit voltage exceeds the permissible
value. Causes:
• poor controller adjustment (overshooting)
• input voltage too high
• interference voltages at the input
• deceleration ramp too short
• braking resistor defective or too small
58
Real speed is bigger than the max. Output speed.
33
Error in the power factor control
46
The drive has driven onto the right limit switch. Programmed
response "Error, restart after reset" (see chapter 6.7
"Response to errors or warning messages").
47
The drive has driven onto the left limit switch. Programmed
response "Error, restart after reset" (see chapter 6.7
"Response to errors or warning messages").
12
Error: General power circuit fault
49
Error: During the initialization the power circuit could not be
recognized or was identified as invalid.
50
Error: Power circuit identification was changed; with a valid
power circuit this error can be reset by writing to SY.3. If the
value displayed in SY.2 is written, only the power-circuit
dependent parameters are reinitialized. If any other value is
written, then the default set is loaded.
22
Error: Parameter value could not be written to the power
circuit. Acknowledgement from PC <> OK
14
Error: Software version for power circuit and control card are
different. Error cannot be reset (only at F5-G B-housing)
23
Sychronization over sercos-bus not possible. Programmed
response "Error, restart after reset" (see chapter 6.7
"Response to errors or warning messages").
39
It has been attempted to select a locked parameter set.
Programmed response "Error, restart after reset" (see
chapter 6.7 "Response to errors or warning messages").
44
The right software limit switch lies outside the defined limits.
Programmed response "Error, restart after reset" (see
chapter 6.7 "Response to errors or warning messages").
45
The left software limit switch lies outside the defined limits.
Programmed response "Error, restart after reset" (see
chapter 6.7 "Response to errors or warning messages").
Error! Overvoltage 1