Special Adjustments - KEB COMBIVERT F5 Instruction Manual

Hide thumbs Also See for COMBIVERT F5:
Table of Contents

Advertisement

Operation of the Unit
GB
3.6
Special
Adjustments
GB
Maximum speed
Step speed 1 and 2
Input I1
Input I2
GB- 20
Value Function
0
track not exchanged
1
track exchanged
2/3
reserved for initiator input
Adjustment range:
Resolution:
Factory setting:
The following parameters serve for the optimization of the drive and the
adaption to certain applications. These adjustments can be ignored at the
initial start-up.
In order to limit the setpoint value a maximum speed must be preset. This
limit value is the basis for further setpoint calculations and for the
determination of setpoint characteristics. The maximum speed limits the
setpoint speed only. Because of speed ripples, speed overshoot or
hardware defects (e.g. defective encoder) the actual speed may exceed
these limits.
Adjustment range:
Resolution:
Factory setting:
Two fixed speeds can be adjusted. The selection is made by the inputs
I1 and I2.
If adjustments are made that are outside the fixed limit of CP.22, then the
speed is internally limited. The negative values are released in application
mode.
Adjustment range:
Resolution:
Factory setting CP.23:
Factory setting CP.24:
Input I1 + input I2 = Step speed 3
(factory setting = 0 rpm)
The Step speed 3 cannot adjusted in the CP mode.
0...3
1
0
0...4000 rpm
0,125 rpm
2100 rpm
-4000...4000 rpm
0,125 rpm
100 rpm
-100 rpm