Viking VFR-500 Manual page 65

Conventional releasing panel
Hide thumbs Also See for VFR-500:

Advertisement

Program #34 Mode
1. Apply power to panel.
2. Press ENT to enter PROGRAM mode
3. Press 6 or scroll down to #6 and press ENT, (The selection is indicated by a flashing arrow next to the number.
4. Enter the password. (Factory default is 1111)
5. Press 1 or press ENT. (1 should be the highlighted selection)
6. The display shows the current program number. Press 1 to change to program 1. Press ENT.
7. Press 1 to accept the change.
8. Press ENT to accept the change.
Single Zone Activation:
Latching Solenoid
Remote Solenoid Reset
OUTPUTS
#1 GENERAL ALARM
#2 RELEASE SOLENOID (2
second pulse)
#3 SOLENOID RESET (2
second pulse)
#4 WATERFLOW BELL
Inputs:
2 Supervisory zones, 2 conventional detection zones, 1 Waterflow zone, 1 Manual release zone, 1 Valve Reset
zone
Outputs:
1 General alarm Indicating, 1 Release circuit, 1 Valve Reset circuit, 1 Waterflow Bell
Operation:
Activation of Supervisory zone 1 or 2 will create a supervisory condition on the panel
Activation of Conventional Detection zone 3 or 4 will activate General alarm output 1 and temporarily activate
release output 2 for two seconds
Activation of Valve Reset zone 5 will temporarily activate release output 3 to reset the solenoid on the preaction
valve and create a supervisory condition
Activation of Waterflow zone 6 will activate the waterflow bell output 4
Activation of Manual Release zone #7 will activate General alarm output 1 and temporarily energize release
output #2
VFR-500 PROGRAM TEMPLATES • 5403799 • REV A • 9/23
#1
#2
Low Air
Valve
Supervisory
Tamper
PROGRAM #34
ZONES
#3
#4
Conventional
Conventional
Detection
Detection
X
X
X
X
65
#5
#6
Valve Reset
Waterflow
Supervisory
X
X
#7
Manual
Release
X
X