Conventional releasing panel
Hide thumbs Also See for VFR-500:

Advertisement

PROGRAM #4
FROM DEDICATED UNSWITCHED
CIRCUIT IN SERVICE PANEL
120VAC-240VAC 50/60 HZ
USE 14AWG OR HEAVIER GAUGE
WIRE WITH 600V INSULATION
LINE
NEUTRAL
EARTH GROUND
BATTERY CABLE
OBSERVE POLARITY
RED +
BLACK -
+
-
POS
NEG
12V BATT.
NOTES:
1. Run field wiring and ensure connections are proper by metering wires. Resistance reading should be 5.1K ohms with end-ofline
resistor (EOLR) at last device. The end-of-line resistor are supplied with the panel Install EOLR on all unused circuits.
2. Connect one circuit at a time and apply AC power.
3. Connect batteries to the panel
4. Press ENT to enter PROGRAM mode
5. Press 6 or scroll down to #6 and press ENT, (The selection is indicated by a flashing arrow next to the number.
6. Enter the password. (Factory default is 1111)
7. Press 1 or press ENT. (1 should be the highlighted selection)
8. The display shows the current program number. Press 4 to change to program 4. Press ENT.
9. Press 1 to accept the change.
10. Press ENT to accept the change
VFR-500 PROGRAM TEMPLATES • 5403799 • REV A • 9/23
FUSE -
4A-250VAC
TIME LAG P-COMM
+
-
A
N
L
PLINK
AC IN CONNECTOR
NON-POWER
LIMITED AND
SUPERVISED
NON-POWER
LIMITED AND
SUPERVISED
OUTPUT
OUTPUT
OUTPUT
1
2
3
BATT
+
-
+
-
POS
NEG
EOL
5.1K
EOL
DIODE
DIODE
EOLR
ASSY
ASSY
12V BATT.
GENERAL
RELEASE
RELEASE
ALARM
SOLENOID
SOLENOID
SYSTEMS1
SYSTEMS
LOW AIR
PRESSURE
VALVE
SUPERVISORY
TAMPER
SWITCH
CONVENTIONAL
SUPERVISORY
SYSTEMS
DETECTION
SYSTEMS
1&2
1&2
09472
EOLR
EOLR
EOLR
5.1K
5.1K
5.1K
B
S
+
-
+
-
+
-
+
-
AUX OUT
ZONE 1
ZONE 2
ZONE 3
PANEL INPUTS (INITIATING ZONES)
CONNECT TO NORMALLY OPEN DEVICES
OR COMPATIBLE 2 WIRE SMOKE
DETECTORS.
MAXIMUM LINE RESISTANCE: 100 OHMS
(EXCEPT WITH LINEAR HEAT DETECTION)
OPTIONAL CA2Z MOUNTING LOCATION
ZONE 5 AND 6 ONLY
OUTPUT
TROUBLE
ALARM
4
COM
NO
NC
COM
NO
RELAY CONTACTS
DRY CONTACTS RATED AT 3A, 30VDC
5.1K
EOLR
WATERFLOW
2
12
WATER
FLOW
MANUAL
SWITCH
RELEASE
09470
STATION
EOLR
EOLR
EOLR
5.1K
5.1K
5.1K
+
-
+
-
+
-
+
-
ZONE 7
ZONE 4
ZONE 5
ZONE 6
+
-
+
-
ZONE 1
OPTIONAL
CA2Z CLASS
A MODULE
CA2Z WILL CONVERT
ZONES 5 AND 6 CLASS B
ZONES INTO CLASS A ZONES
OPTIONAL CLASS A
CONNECTIONS EOLR IS
NOT USED FOR CLASS A
WTRFL
SUPV
RELEASE
NC
COM
NO
NC
COM
NO
NC
Legend
S
+
-
+
-
ZONE 2
N.O. Initiating Device
Conventional Detection
Notification Appliance
Solenoid
End-of-Line Diode Assy