Release control panel

Advertisement

Quick Links

June 21, 1993
1. PRODUCT NAME
Viking Model B-1
Release Control Panel
1991 -
2. MANUFACTURED FOR
THE VIKING CORPORATION
210 N. Industrial Park Road
Hastings, Michigan 49058 U.S.A.
Telephone:
(616) 945-9501
(800) 968-9501
Fax Number:
(616) 945-9599
From outside U.S.A.
Telephone: +1 (616) 945-9501
Fax Number: +1 (616) 945-9599
3. PRODUCT DESCRIPTION
The Viking Model B-1 Par-3 Panel is a
supervised, 24 Volt, microprocessor-
controlled Release Control Panel. The
panel is designed to operate up to two
electric release devices, (usually sole-
noid valves), in the release piping of
deluge or preaction systems. The panel
is available for use with either 120 VAC
or 230 VAC power supplies. A built-in
battery compartment holds two 12 Volt
batteries which are charged by an inter-
nal battery charger. Batteries are avail-
able to provide up to 90 hours of backup
power during AC power failure.
The Model B-1 panel can be used with
a wide range of compatible initiating de-
vices such as heat (including linear heat
detection systems such as Protectowire
Systems), photoelectric, ionization, and
smoke detectors.
A dip switch 'Function Selector' allows
field programming for one of four possible
input/output combinations (see Table 1).
Note: Units of measure in parentheses may be approximations.
Form No. 063092
R
TECHNICAL DATA
In fire conditions when an initiating de-
vice circuit (or predetermined combina-
tion of circuits) is energized, the panel
activates a combination of release de-
vice circuits and alarm circuits according
to the 'Function Selector' setting. On the
panel's display board, the appropriate
Alarm, Trouble, and Supervisory LED's
will flash until the event has been ac-
knowledged. After depressing the Tone
or Alarm Silence button, the LED will
remain steadily illuminated until the
panel is reset.
4. AVAILABILITY AND SERVICE
The Viking Model B-1 Par-3 Release
Control Panel is available through a net-
work of Domestic, Canadian, and Inter-
national Distributors. See the Yellow
Pages of the telephone directory for
closest distributor (listed under "Sprin-
klers Automatic Fire") or contact The
Viking Corporation.
5. GUARANTEES
Viking agrees to repair or replace goods
found to be defective in material and
workmanship for a period of one year
from the date of shipment. For details of
warranty, refer to price list.
Model
Name
B-1
Par-3
110 VAC 50/60Hz
B-1
Par-3C
110 VAC 50/60Hz
B-1
Par-3E
220VAC 50/60 Hz
1
UL listed Releasing Device Control Unit (UOJZ) Model B-1
2
ULC listed and CSA approved Par-3C
3
Accepted by City of New York Department of Buildings MEA 89-92-E when configured for
Single Hazard-Two Zone operation (see TABLE 1) and equipped with LED Interface Module (4XLM)
and Remote Annunciator (RZA-4X). See ACCESSORIES.
6. TECHNICAL DATA
Approvals
See Approval Chart
Cabinet
Steel: Painted red for identification pur-
poses
Vented enclosure
Environment:
Temperature: 32
Humidity: 85% Relative Humidity
(non-condensing) at 90
maximum
See ACCESSORIES for wall trim avail-
able from Viking.
Dimensions:
Backbox: 16" (406mm) high, 14.5"
(368mm) wide, 4.75" (121mm) deep.
Door: 16.125" (410mm) high, 14.625"
(372mm) wide.
Cabinet: 5.375" (137mm) deep.
AC Power
Par-3 and Par-3C: 120 VAC, 50/60 Hz,
1.2 amps
Wire size: minimum #14 AWG with 600
V insulation
Par-3E: 230 VAC, 50 Hz, 0.65 amps
Wire size: minimum #14 AWG with 600
V insulation
APPROVAL CHART
Power Supply Viking Part No. UL
07907
07953
07908
Panel 210 a
MODEL B-1
RELEASE CONTROL
PANEL
o
o
o
F (0
C) to120
F (48
o
F (32
APPROVALS
1
2
ULC
FM NYC
Yes
--
Yes
Yes
--
Yes
--
--
--
Yes
New issue June 21, 1993
o
C)
o
C)
3
--
--

Advertisement

loading

Summary of Contents for Viking B-1

  • Page 1 Systems), photoelectric, ionization, and smoke detectors. A dip switch ’Function Selector’ allows UL listed Releasing Device Control Unit (UOJZ) Model B-1 ULC listed and CSA approved Par-3C field programming for one of four possible Accepted by City of New York Department of Buildings MEA 89-92-E when configured for input/output combinations (see Table 1).
  • Page 2: Technical Data

    Input 2: Detection Circuit set switch is pushed, they will re-ac- on release circuits. Input 3: Waterflow (Alarm Pressure Sw) Contact the Viking Distributor for a list of tivate the panel. Input 4: Supervisory Circuit compatible indicating appliances and Front Panel Zone Status LEDs Power limited circuitry releasing devices.
  • Page 3: Installation

    Connectors on one standby battery requirements. the Model B-1 Release Control plug/wire assembly fit 7.0 AH Batter- Zone Relay Module (4XZM): Model B-1 Panel. ies. Connectors other panels can accommodate a second Contact the Viking Distributor for a list plug/wire assembly fit 12.0 AH Bat-...
  • Page 4 Waterflow "Authority Having Jurisdiction" may 2: Operate individual detectors, fol- To test Water Flow Alarm on Viking pre- have additional maintenance, testing, lowing instructions listed in techni- action and Viking deluge systems: Con- and inspection requirements which must cal data for the detector used.
  • Page 5 June 21, 1993 Panel 210 e MODEL B-1 TECHNICAL DATA RELEASE CONTROL PANEL TABLE 1 Dip Switch Settings for System Configuration Modes Note: Dip Switches 3, 4, and 5 MUST be OFF to disable timer capabilities of the panel. For information concerning timer capabilities, refer to PAR-3 Owners Manual.
  • Page 6 June 21, 1993 Panel 210 f MODEL B-1 TECHNICAL DATA RELEASE CONTROL PANEL Figure 1 Form No. 063092...