Program #24 Mode
1. Apply power to panel.
2. Press ENT to enter PROGRAM mode
3. Press 6 or scroll down to #6 and press ENT, (The selection is indicated by a flashing arrow next to the number.
4. Enter the password. (Factory default is 1111)
5. Press 1 or press ENT. (1 should be the highlighted selection)
6. The display shows the current program number. Press 1 to change to program 1. Press ENT.
7. Press 1 to accept the change.
8. Press ENT to accept the change.
Single Hazard, 2
Dectection Zones, 1
Manual Release Zone and
A Discharge Confirmation
Zone
OUTPUTS
#1 ALARM INDICATING
#2 ALARM INDICATING
#3 RELEASE
#4 SUPERVISORY
Description:
Single Hazard, 2 detection zones, a manual station zone and a discharge confirmation zone.
Inputs:
1 supervisory zone, 1 low air zone, 2 detection zones, 1 manual station zone, 1 abort circuit
Outputs:
2 general alarm, 1 release circuit, 1 supervisory
Operation:
Activation of either detection zones 3 or 4 will activate the alarm output #1 and start the pre-discharge timer for
the release circuit output #3
Activation of the manual release zone #5 will activate the alarm output #2 and start the manual release pre-
discharge timer for release circuit output #3
Activation of zone 6 will operate output #4
When either zone 3 or 4 is in alarm, output 1 will operate and the pre-discharge timer for output #3 will start
When zone 5 is in alarm, output 2 will operate and the manual release pre-discharge timer for output #3 will
start.
When zone 6 is activated, output #4 will operate
VFR-500 PROGRAM TEMPLATES • 5403799 • REV A • 9/23
#1
#2
Abort
Supervisory
X
PROGRAM #24
CONVENTIONAL INPUT ZONES
#3
#4
Detection
Detection
X
X
X
X
55
#5
#6
Manual
Low Air
Release
Supervisory
X
X
X