Conventional releasing panel
Hide thumbs Also See for VFR-500:

Advertisement

Program #21 Mode
1. Apply power to panel.
2. Press ENT to enter PROGRAM mode
3. Press 6 or scroll down to #6 and press ENT, (The selection is indicated by a flashing arrow next to the number.
4. Enter the password. (Factory default is 1111)
5. Press 1 or press ENT. (1 should be the highlighted selection)
6. The display shows the current program number. Press 21 to change to program 21. Press ENT.
7. Press 1 to accept the change.
8. Press ENT to accept the change.
Dual Hazard, 2 Detection
Zones Mapped to 1
Release Circuit and 2
Other Detection Zones
Mapped to a Separate
Release Circuit, 1
Supervisory Circuit, 1
Abort Circuit
OUTPUTS
#1 ALARM INDICATING
#2 RELEASE
#3 ALARM INDICATING
#4 RELEASE
Description:
Dual Hazard, 2 detection zones mapped to 1 release circuit and 2 other detection zones mapped to another release
circuit
Inputs:
1 supervisory zone, 4 detection zones, 1 abort circuit
Outputs:
2 general alarm, 2 release circuit
Operation:
Activation of either detection zone 3 or 4 will activate the alarm output #1 and start the pre-discharge timer for
the release circuit output #2
Activation of either detection zone 5 or 6 will activate the alarm output #3 and start the pre-discharge timer for
the release circuit output #2
When either zone 3 or 4 is in alarm, outputs 1 & 2 will operate
When either zone 5 or 6 is in alarm, outputs 3 & 4 will operate
VFR-500 PROGRAM TEMPLATES • 5403799 • REV A • 9/23
#1
#2
Abort
Supervisory
PROGRAM #21
CONVENTIONAL INPUT ZONES
#3
#4
Detection
Detection
X
X
X
X
49
#5
#6
Detection
Detection
X
X
X
X
#7
Unused