Conventional releasing panel
Hide thumbs Also See for VFR-500:

Advertisement

PROGRAM #14
FROM DEDICATED UNSWITCHED
CIRCUIT IN SERVICE PANEL
120VAC-240VAC 50/60 HZ
USE 14AWG OR HEAVIER GAUGE
WIRE WITH 600V INSULATION
LINE
NEUTRAL
EARTH GROUND
BATTERY CABLE
OBSERVE POLARITY
RED +
BLACK -
+
-
POS
NEG
12V BATT.
NOTES:
1. Run field wiring and ensure connections are proper by metering wires. Resistance reading should be 5.1K ohms with end-ofline
resistor (EOLR) at last device. The end-of-line resistor are supplied with the panel Install EOLR on all unused circuits.
2. Connect one circuit at a time and apply AC power.
3. Connect batteries to the panel
4. Press ENT to enter PROGRAM mode
5. Press 6 or scroll down to #6 and press ENT, (The selection is indicated by a flashing arrow next to the number.
6. Enter the password. (Factory default is 1111)
7. Press 1 or press ENT. (1 should be the highlighted selection)
8. The display shows the current program number. Press 14 to change to program 14. Press ENT.
9. Press 1 to accept the change.
10. Press ENT to accept the change
VFR-500 PROGRAM TEMPLATES • 5403799 • REV A • 9/23
FUSE -
4A-250VAC
TIME LAG P-COMM
+
-
A
N
L
PLINK
AC IN CONNECTOR
NON-POWER
LIMITED AND
SUPERVISED
NON-POWER
LIMITED AND
SUPERVISED
OUTPUT
OUTPUT
OUTPUT
1
2
3
BATT
+
-
+
-
POS
NEG
5.1K
5.1K
EOL
EOLR
DIODE
EOLR
ASSY
12V BATT.
RELEASE
SUPERVISORY
GENERAL
/
LOW AIR
SOLENOID
ALARM
TAMPER
LOW AIR
PRESSURE
SUPERVISORY
VALVE
SWITCH
CONVENTIONAL
TAMPER
0947
3
DETECTION
SUPERVISORY
EOLR
EOLR
EOLR
5.1K
5.1K
5.1K
B
S
+
-
+
-
+
-
+
-
AUX OUT
ZONE 1
ZONE 2
ZONE 3
PANEL INPUTS (INITIATING ZONES)
CONNECT TO NORMALLY OPEN DEVICES
OR COMPATIBLE 2 WIRE SMOKE
DETECTORS.
MAXIMUM LINE RESISTANCE: 100 OHMS
(EXCEPT WITH LINEAR HEAT DETECTION)
OPTIONAL CA2Z MOUNTING LOCATION
ZONE 5 AND 6 ONLY
OUTPUT
TROUBLE
ALARM
4
COM
NO
COM
NO
NC
RELAY CONTACTS
DRY CONTACTS RATED AT 3A, 30VDC
EOL
DIODE
ASSY
RELEASE
2
1
SOLENOID
32
WAT
R
FLOW
E
MANUAL
RELEASE
SWITCH
STATION
09470
EOLR
EOLR
EOLR
5.1K
5.1K
5.1K
+
-
+
-
+
-
+
-
ZONE 7
ZONE 4
ZONE 5
ZONE 6
+
-
+
-
ZONE 1
OPTIONAL
CA2Z CLASS
A MODULE
CA2Z WILL CONVERT
ZONES 5 AND 6 CLASS B
ZONES INTO CLASS A ZONES
OPTIONAL CLASS A
CONNECTIONS EOLR IS
NOT USED FOR CLASS A
WTRFL
SUPV
RELEASE
NC
COM
NO
NC
COM
NO
NC
Legend
S
+
-
+
-
ZONE 2
N.O. Initiating Device
Conventional Detection
Notification Appliance
Solenoid
End-of-Line Diode Assy