Download Print this page

Viking VFR-500 Manual page 59

Conventional releasing panel
Hide thumbs Also See for VFR-500:

Advertisement

Program #31 Mode
1. Apply power to panel.
2. Press ENT to enter PROGRAM mode
3. Press 6 or scroll down to #6 and press ENT, (The selection is indicated by a flashing arrow next to the number.
4. Enter the password. (Factory default is 1111)
5. Press 1 or press ENT. (1 should be the highlighted selection)
6. The display shows the current program number. Press 31 to change to program 31. Press ENT.
7. Press 1 to accept the change.
8. Press ENT to accept the change.
Failsafe Operation
Single zone activation
Two solenoids, one is
Normally Energized
OUTPUTS
#1 ALARM INDICATING
(General Alarm)
#2 RELEASE
NORMALLY
ENERGIZED
(Failsafe Solenoid, Drops
Out on Any System
Trouble)
#3 RELEASE (Solenoid)
#4 ALARM (waterflow
alarm)
Inputs:
3 Supervisory zones, 2 conventional detection zones, 1 Waterflow zone, 1 Manual release zone
Outputs:
1 General alarm Indicating, 1 Release Circuit: Normally Energized. Failsafe, De-energizes on any system
trouble, 1 Release Circuit: Normally Not Energized, 1 Waterflow alarm output.
Operation:
Output 2 is constantly energized. Any trouble condition on the panel will de-energize output 2. Activation of
Supervisory zone 1, zone 2 or Low Diaphragm water Pressure zone 5, will create a supervisory condition on the
panel.
Activation of Conventional Detection zone 3 or zone 4, or Manual Release zone 7 will activate General alarm
output 1, De-energize output 2 and energize/activate release output 3.
Activation of Waterflow zone 6 will activate General alarm output 1 and Waterflow alarm output 4.
Activation of Manual Release zone #7 will activate General alarm output 1, de-energize failsafe release output 2
and energize/activate release output #3.
VFR-500 PROGRAM TEMPLATES • 5403799 • REV A • 9/23
#1
#2
VALVE TAMPER
LOW AIR
SUPERVISORY
SUPERVISORY
PROGRAM #31
CONVENTIONAL INPUT ZONES
#3
#4
CONVENTIONAL
CONVENTIONAL
DETECTION
DETECTION
X
X
X
X
X
X
59
#5
#6
SUPERVISORY
WATER LOW
X
X
#7
MANUAL
RELEASE
X
X
X

Advertisement

loading