Viking VFR-500 Manual page 4

Conventional releasing panel
Hide thumbs Also See for VFR-500:

Advertisement

To enable Class A on zones 3 or 4:
1.
Install IDC-6 with address 16 as described on pg. 3-23
2.
Press ENT
3.
Enter 8 or scroll down to PANEL SETUP, indicated by a flashing  and press ENT
4.
Enter the password. Factory default is 1111.
5.
Enter 2 or scroll down to LEARN MENU, indicated by a flashing  and press ENT
6.
Press 1 OR ENT to select LEARN ALL
The panel will search for connected devices
7.
Press 1 or ENT to select P-LINK FOUND to review devices
Addr 16 (IDC-6)
8.
Press ESC to exit learn all menu
9.
Press 1 to Accept the new devices
10.
Press ENT to accept the change and update the panel
11.
Press ENT
12.
Enter 8 or scroll down to PANEL SETUP, indicated by a flashing  and press ENT
13.
Enter the password. Factory default is 1111.
14.
Enter 7 or scroll down to IDC6 F/CA ZONE 3, indicated by a flashing  and press ENT
15.
Press any key to accept
16.
Press ESC to exit PANEL SETUP menu
17.
Press 1 to Accept
18.
Press ENT to accept the change and update the panel
Repeat steps 11 – 18 using 8 or scroll down to IDC6 F/CA ZONE 4 to enable class A for zone 4. Zone 3 class A wiring to INPUT
3 / INPUT 4 on IDC-6 address 16 as shown on page 3-24. Zone 4 class A wiring to INPUT 5 / INPUT 6 on IDC-6 address 16.
When using standard program templets IDC-6 address 16 INPUTS 1 and INPUT 2 are unused.
VFR-500 PROGRAM TEMPLATES • 5403799 • REV A • 9/23