Viking VFR-500 Manual page 36

Conventional releasing panel
Hide thumbs Also See for VFR-500:

Advertisement

PROGRAM #16
NOTES:
1. Run field wiring and ensure connections are proper by metering wires. Resistance reading should be 5.1K ohms with end-ofline
resistor (EOLR) at last device. The end-of-line resistor are supplied with the panel Install EOLR on all unused circuits.
2. Connect one circuit at a time and apply AC power.
3. Connect batteries to the panel
4. Press ENT to enter PROGRAM mode
5. Press 6 or scroll down to #6 and press ENT, (The selection is indicated by a flashing arrow next to the number.
6. Enter the password. (Factory default is 1111)
7. Press 1 or press ENT. (1 should be the highlighted selection)
8. The display shows the current program number. Press 16 to change to program 16. Press ENT.
9. Press 1 to accept the change.
10. Press ENT to accept the change
Note: Release solenoids #1 and #2 shall be wired in parallel and connected to output #3. the wiring shall be in conduit orotherwise
protected. Any connections shall be made in a junction box. This may not conform to the monitoring for integrity
requirements for NFPA 72.
VFR-500 PROGRAM TEMPLATES • 5403799 • REV A • 9/23
FROM DEDICATED UNSWITCHED
CIRCUIT IN SERVICE PANEL
120VAC-240VAC 50/60 HZ
USE 14AWG OR HEAVIER GAUGE
WIRE WITH 600V INSULATION
LINE
NEUTRAL
EARTH GROUND
FUSE -
4A-250VAC
TIME LAG P-COMM
+
-
N
L
PLINK
AC IN CONNECTOR
NON-POWER
LIMITED AND
SUPERVISED
NON-POWER
LIMITED AND
SUPERVISED
OUTPUT
OUTPUT
OUTPUT
1
2
BATT
+
-
BATTERY CABLE
OBSERVE POLARITY
RED +
BLACK -
+
-
+
-
POS
NEG
POS
NEG
5.1K
EOL
5.1K
EOLR
DIODE
EOLR
ASSY
12V BATT.
12V BATT.
GENERAL
SUPERVISORY
RELEASE
ALARM
LOW AIR/
SOLENOID
TAMPER
1&2
36
LOW AIR
FIRECYCLE
PRESSURE
LOW AIR
DETECTORS
A
A L
VALVE
TAMPER
SWITCH
SUPERVISORY
0947 3
0947 3
SUPERVISORY
EOLR
EOLR
EOLR
EOLR
5.1K
5.1K
5.1K
5.1K
CONVENTIONAL
DETECTION
A
B
S
+
-
+
-
+
-
+
-
+
AUX OUT
ZONE 1
ZONE 2
ZONE 3
ZONE 4
PANEL INPUTS (INITIATING ZONES)
CONNECT TO NORMALLY OPEN DEVICES
OR COMPATIBLE 2 WIRE SMOKE
DETECTORS.
MAXIMUM LINE RESISTANCE: 100 OHMS
(EXCEPT WITH LINEAR HEAT DETECTION)
OPTIONAL CA2Z MOUNTING LOCATION
ZONE 5 AND 6 ONLY
OUTPUT
TROUBLE
ALARM
3
4
COM
NO
NC
COM
NO
NC
RELAY CONTACTS
DRY CONTACTS RATED AT 3A, 30VDC
EOL
DIODE
ASSY
Legend
N
/O
SOLENOID
S
S
WATER
MANUAL
R M
FLOW
SWITCH
RELEASE
STATION
09470
EOLR
EOLR
5.1K
5.1K
-
+
-
+
-
+
-
ZONE 5
ZONE 6
ZONE 7
WTRFL
SUPV
RELEASE
COM
NO
NC
COM
NO
NC
N.O. Initiating Device
Firecycle Detector
Notification Appliance
Solenoid
End-of-Line Diode Assy