Viking VFR-500 Manual page 47

Conventional releasing panel
Hide thumbs Also See for VFR-500:

Advertisement

Program #20 Mode
1. Apply power to panel.
2. Press ENT to enter PROGRAM mode
3. Press 6 or scroll down to #6 and press ENT, (The selection is indicated by a flashing arrow next to the
number.
4. Enter the password. (Factory default is 1111)
5. Press 1 or press ENT. (1 should be the highlighted selection)
6. The display shows the current program number. Press 20 to change to program 20. Press ENT.
7. Press 1 to accept the change.
8. Press ENT to accept the change.
Dual Hazard, 2 Detection
Zones Cross-Zoned to 1
Release Circuit, 2 Other
Detection Zones Cross-
Zoned to a Separate Release
Circuit, 1 Supervisory
Circuit, 1 abort circuit
OUTPUTS
#1 ALARM INDICATING
#2 RELEASE
#3 ALARM INDICATING
#4 RELEASE
* Release Outputs which are Cross-Zoned need a Software Zone in order to work properly. The Software Zone Number will be dis-
played upon a release.
XX = Cross-Zoned
Description:
Dual Hazard, 2 detection zones cross-zoned to 1 release circuit and 2 other detection zones cross zoned to
another release circuit
Inputs:
1 supervisory zone, 4 detection zones, 1 abort circuit
Outputs:
2 general alarm, 2 release circuit
Operation:
Activation of either detection zones 3 or 4 will activate the alarm output #1
Activation of both detection circuits 3 and 4 at the same time will start the pre-discharge timer for release circuit
output #2 as well as activate the alarm output #1
Activation of either detection zones 5 or 6 will activate the alarm output #3
Activation of both detection circuits 5 and 6 at the same time will start the pre-discharge timer for release circuit
output #4 as well as activate the alarm output #3
When either zone 3 or 4 is in alarm, output 1 will operate
When both zones 3 and 4 are in alarm at the same time, the pre-discharge timer for output #2 will operate
When either zone 5 or 6 is in alarm, output 3 will operate
When both zones 5 and 6 are in alarm at the same time, the pre-discharge timer for output #4 will operate
VFR-500 PROGRAM TEMPLATES • 5403799 • REV A • 9/23
CONVENTIONAL INPUT ZONES
#1
#2
Abort
Supervisory
Detection
XX
PROGRAM #20
#3
#4
#5
Detection Detection
X
X
XX
X
XX
47
SOFTWARE ZONES
#6
#7
#8
Detection
Unused
Release
Zone Type
X
XX*
X
XX
#9
Release
Zone Type
X
XX*