Program #33 Mode
1. Apply power to panel.
2. Press ENT to enter PROGRAM mode
3. Press 6 or scroll down to #6 and press ENT, (The selection is indicated by a flashing arrow next to the number.
4. Enter the password. (Factory default is 1111)
5. Press 1 or press ENT. (1 should be the highlighted selection)
6. The display shows the current program number. Press 33 to change to program 33. Press ENT.
7. Press 1 to accept the change.
8. Press ENT to accept the change.
Redundant Solenoids
Single Interlock with Single
Zone Activation
OUTPUTS
#1 GENERAL ALARM
#2 WATERFLOW ALARM
#3 RELEASE SOLENOID
#4 RELEASE SOLENOID
Inputs:
3 Supervisory zones, 2 Detection zones, 1 Waterflow zone, 1 Manual Release zone
Outputs:
1 General Alarm, 1 Waterflow, 2 Release Solenoids
Operation:
Activation of any supervisory zone or Low Air Alarm zone will create a supervisory condition on the panel, no
outputs will activate
Activation of Conventional Detection zone 3 and/or 4 and/or Manual Release zone 7 will activate General
Alarm output 1 and Release Solenoid outputs 3 and 4
Activation of Waterflow zone 6 will activate General alarm output 1 and Waterflow output 2
VFR-500 PROGRAM TEMPLATES • 5403799 • REV A • 9/23
#1
#2
Low Air
Valve
Supervisory
Tamper
PROGRAM #33
ZONES
#3
#4
Conventional
Conventional
Detection
Detection
X
X
X
X
X
X
63
#5
#6
Low Air
Waterflow
Manual
Alarm
Release
X
X
#7
X
X
X