Viking VFR-500 Manual page 6

Conventional releasing panel
Hide thumbs Also See for VFR-500:

Advertisement

Wiring Diagram Programs
PROGRAM #1
FROM DEDICATED UNSWITCHED
CIRCUIT IN SERVICE PANEL
120VAC-240VAC 50/60 HZ
USE 14AWG OR HEAVIER GAUGE
WIRE WITH 600V INSULATION
LINE
NEUTRAL
EARTH GROUND
BATTERY CABLE
OBSERVE POLARITY
RED +
BLACK -
NOTES:
1. Run field wiring and ensure connections are proper by metering wires. Resistance reading should be 5.1K ohms with end-ofline
resistor (EOLR) at last device. The end-of-line resistor are supplied with the panel Install EOLR on all unused circuits.
2. Connect one circuit at a time and apply AC power.
3. Connect batteries to the panel
4. Press ENT to enter PROGRAM mode
5. Press 6 or scroll down to #6 and press ENT, (The selection is indicated by a flashing arrow next to the number.
6. Enter the password. (Factory default is 1111)
7. Press 1 or press ENT. (1 should be the highlighted selection)
8. The display shows the current program number. Press 1 to change to program 1. Press ENT.
9. Press 1 to accept the change.
10. Press ENT to accept the change
VFR-500 PROGRAM TEMPLATES • 5403799 • REV A • 9/23
FUSE -
4A-250VAC
TIME LAG P-COMM
+
-
N
L
PLINK
AC IN CONNECTOR
NON-POWER
LIMITED AND
SUPERVISED
NON-POWER
LIMITED AND
SUPERVISED
OUTPUT
OUTPUT
OUTPUT
1
2
BATT
+
-
+
-
+
-
POS
NEG
POS
NEG
5.1K
5.1K
EOLR
EOLR
DIODE
ASSY
12V BATT.
12V BATT.
GENERAL
WATERFLOW
RELEASE
ALARM
SOLENOID
LOW AIR
PRESSURE
SUPERVISORY
VALVE
CONVENTIONAL
SWITCH
TAMPER
DETECTION
09472
SUPERVISORY
EOLR
EOLR
EOLR
5.1K
5.1K
5.1K
A
B
S
+
-
+
-
+
-
+
-
+
AUX OUT
ZONE 1
ZONE 2
ZONE 3
ZONE 4
PANEL INPUTS (INITIATING ZONES)
CONNECT TO NORMALLY OPEN DEVICES
OR COMPATIBLE 2 WIRE SMOKE
DETECTORS.
MAXIMUM LINE RESISTANCE: 100 OHMS
(EXCEPT WITH LINEAR HEAT DETECTION)
OPTIONAL CA2Z MOUNTING LOCATION
ZONE 5 AND 6 ONLY
OUTPUT
ALARM
TROUBLE
3
4
COM
NO
NC
COM
NO
RELAY CONTACTS
DRY CONTACTS RATED AT 3A, 30VDC
EOL
5.1K
EOLR
SUPERVISORY
BELL
6
WATER
FLOW
MANUAL
SWITCH
RELEASE
09470
STATION
EOLR
EOLR
EOLR
5.1K
5.1K
5.1K
-
+
-
+
-
+
-
ZONE 5
ZONE 6
ZONE 7
+
-
+
-
+
-
+
-
ZONE 1
ZONE 2
OPTIONAL
CA2Z CLASS
A MODULE
CA2Z WILL CONVERT
ZONES 5 AND 6 CLASS B
ZONES INTO CLASS A ZONES
OPTIONAL CLASS A
CONNECTIONS EOLR IS
NOT USED FOR CLASS A
WTRFL
SUPV
RELEASE
NC
COM
NO
NC
COM
NO
NC
Legend
Initiating device
Notification appliance
Solenoid
S
End-of-Line diode assy