Viking VFR-500 Manual page 67

Conventional releasing panel
Hide thumbs Also See for VFR-500:

Advertisement

Program #35 Mode
1. Apply power to panel.
2. Press ENT to enter PROGRAM mode
3. Press 6 or scroll down to #6 and press ENT, (The selection is indicated by a flashing arrow next to the number.
4. Enter the password. (Factory default is 1111)
5. Press 1 or press ENT. (1 should be the highlighted selection)
6. The display shows the current program number. Press 1 to change to program 1. Press ENT.
7. Press 1 to accept the change.
8. Press ENT to accept the change.
Latching Solenoid
Cross Zoned
OUTPUTS
VALVE TAMPER
SUPERVISORY
#1 GENERAL
ALARM
#2 RELEASE
SOLENOID (2
second pulse)
#3 SOLENOID
RESET (2 second
pulse)
#4 WATERFLOW
BELL
* Release Outputs which are Cross-Zoned need a Pseudo Zone in order to work properly. The Pseudo Zone Number will be displayed upon
.
a release
XX = Cross-Zoned
Inputs:
2 Supervisory zones, 1 conventional detection zone, 1 Low Air Alarm zone, 1 Waterflow zone, 1 Manual release
zone, 1 Valve reset zone
Outputs:
1 General alarm Indicating, 1 Release circuit, 1 Valve Reset circuit, 1 Waterflow Bell
Operation:
Activation of Conventional Detection zone #3 and Low Air Alarm zone #4 at the same time or activation of
Manual Release zone #7 will activate and energize release output #2
Activation of Low Air Alarm zone 4 will create a supervisory condition on the panel
Activation of Valve Reset zone 5 will reset the solenoid on the preaction valve for two seconds
Activation of Waterflow zone 6 will activate the waterflow bell output 4
VFR-500 PROGRAM TEMPLATES • 5403799 • REV A • 9/23
CONVENTIONAL INPUT ZONES
#1
#2
LOW AIR
CONVENTIONAL
SUPERVISORY
DETECTION
PROGRAM #35
#3
#4
LOW AIR
VALVE RESET
ALARM
SUPERVISORY
X
XX
XX
67
#5
#6
#7
WATER
MANUAL
FLOW
RELEASE
X
X
X
X
SOFTWARE
ZONES
#8
RELEASE ZONE
TYPE
X
XX*