Viking VFR-500 Manual page 41

Conventional releasing panel
Hide thumbs Also See for VFR-500:

Advertisement

Viking Sprinkler
2 Release Zones,
System Types
Waterflow Zone,
(UK Only)
& Manual Release
Zone
OUTPUTS
(Indicating Circuits)
Supervisory Zone
#1 General Alarm
#2 Waterflow
#3 Release Solenoid
#4 Supervisory Bell
Inputs:
2 Conventional Detection zones, 1 Waterflow zone, 1 Manual Release zone, 2 Supervisory zones
Outputs:
1 General Alarm, 1 Waterflow Alarm, 1 Solenoid Release, 1 Supervisory Bell
Operation:
Activation of Conventional Detection zone #3 or #4 or Manual Release zone #6 will activate output #3
(Release Solenoid) and output #1 (General Alarm)
Activation of Waterflow zone #5 will activate output #2 (Waterflow) and output #1 (General Alarm)
Activation of Low Air Supervisory zone #1 or Valve Tamper Supervisory zone #2 will operate output #4
(Supervisory Bell).
NOTES:
1.Connect EOL Diode assembly IN SERIES as shown with solenoids on outputs #3. Black wire to negative terminal on panel
Red wire through solenoid to positive terminal on panel. Output #3 has 2 solenoids. These must be connected in parallel and
the EOL diode is connected in series with the parallel solenoids..
2. Polarity is shown on indicating circuits in an activated (in alarm) condition.
3. Install EOLR (provided) on all unnused circuits.
4. See the instruction manual for circuit information, panel limits, and battery sizing.
5. For wire routing instructions through the releasing panel, see Fig 1 on page 2-7 of the instruction manual.
6. See instruction manual for proper programming.
7. See instruction manual for list of compatible smoke detectors.
8. See specific system type data page for proper pressure switch settings.
9. For UL864 Approved Programming Options, see page 6-102.
VFR-500 PROGRAM TEMPLATES • 5403799 • REV A • 9/23
PROGRAM #18
For One Sprinkler System
1. Single Interlocked Preaction System with Electric Release
2. Deluge System with Electric Release
3. Non-Interlocked Preaction System with Electric Release
4. Double Interlocked Preaction System with Electric/Pneumatic Release
#1
#2
Low Air
Valve Tamper
Supervisory
Zone
X
X
OPERATION DESCRIPTION
ZONES (Initiating Circuits)
#3
#4
Conventional
Conventional
Detection
Detection
Zone
Zone
X
X
X
X
41
#5
#6
#7
Waterflow
Manual
Unused
Zone
Release
Zone
X
X
X
X