Viking VFR-500 Manual page 17

Conventional releasing panel
Hide thumbs Also See for VFR-500:

Advertisement

Viking Sprinkler
Release Zone
System Types
Release Zone
OUTPUTS
(Indicating Circuits)
#1 General Alarm
#2 Supervisory Bell
#3 Release Solenoid
#4 N/O Solenoid
Inputs:
FIRECYCLE Detector zone, Low Air Alarm zone, 1 Waterflow zone,1 Manual Release zone, 2
Supervisory zones
Outputs:
1 General Alarm, 1 Supervisory Alarm, 1 Release Solenoid, and 1 N/O Solenoid
Operation:
Activation of FIRECYCLE Detector zone #3 will activate output #1 (General Alarm), output #3
(Release Solenoid), and output #4 (N/O Solenoid)
Activation of Low Air Alarm zone #4 will activate output #2 (Supervisory Bell) and output #4 (N/O
Solenoid)
Activation of Waterflow zone #5 will activate output #1 (General Alarm) and output #4 (N/O
Solenoid)
Activation of Manual Release zone #6 will activate output #1 (General Alarm) and output #3 (Release
Solenoid)
Deactivation of FIRECYCLE Detector zone #3 will start soak timer, when timer cycle is complete
output #3 (Release Solenoid) is deactivated
Activation of Low Air Supervisory Zone #1 or Valve Tamper Supervisory zone #2 will activate output
#2 (Supervisory Bell)
NOTES:
1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid) and output #4 (N/O
Solenoid). Black wire to negative terminal on panel and Red wire through Solenoid to positive terminal on panel.
2. Polarity is shown on indicating circuits in an activated (in alarm) condition.
3. Install EOLR (provided) on all unnused circuits.
4. See the instruction manual for circuit information, panel limits, and battery sizing.
5. For wire routing instructions through the releasing panel, see Fig 1 on page 2-7 of the instruction manual.
6. See instruction manual for proper programming.
7. See specific system type data page for proper pressure switch settings.
8. Connect EOL resistor after last FIRECYCLE detector on return line to common terminal in FIRECYCLE Detector zone #1.
9. Set the soak timer to desired duration period. Factory setting is continuous. Recommend 60 seconds minimum.
10. Loss of DC power below 20 volt causes output #3 (Release Solenoid) and output #4 (N/O Solenoid) to drop out.
11. Use only Viking FIRECYCLE detectors on FIRECYCLE Detector zone #1.
12. Refer to Viking technical data sheet F_051304 for Firecycle single interlock multi-cycle operation.
13. For UL864 Approved Programming Options, see page 6-102.
VFR-500 PROGRAM TEMPLATES • 5403799 • REV A • 9/23
For One Sprinkler System
1. FIRECYCLE III Single Interlocked Preaction Multicycle System
and Manual
2. FIRECYCLE III Single Interlocked Preaction Multicycle System - NYC Special
#1
#2
Low Air
Valve Tamper
Supervisory
Supervisory
Zone
Zone
X
X
OPERATION DESCRIPTION
PROGRAM #6
ZONES (Initiating Circuits)
#3
#
FIRECYCLE
Low Air
Detector Zone
Alarm Zone
X
X
X
X
X
17
#5
#6
Waterflow
Manual
Zone
Release Zone
X
X
X
X
#7
Unused