Download Print this page

Viking VFR-500 Manual page 56

Conventional releasing panel
Hide thumbs Also See for VFR-500:

Advertisement

Wiring Diagram Program #30
Failsafe Single Hazard Cross Zoned, -2 Alarm Zones, 1 Waterflow
Zone, 2 supervisory Zones with Manual Release
FROM DEDICATED UNSWITCHED
CIRCUIT IN SERVICE PANEL
120VAC-240VAC 50/60 HZ
USE 14AWG OR HEAVIER GAUGE
WIRE WITH 600V INSULATION
LINE
NEUTRAL
EARTH GROUND
AC IN CONNECTOR
LIMITED AND
BATTERY CABLE
OBSERVE POLARITY
BLACK -
POS
NEG
12V BATT.
NOTES:
1. Connect only UL Listed 24VDC devices to indicating
circuits.
2. Connect EOL Diode assembly IN SERIES with solenoid
on release circuit
3. Install EOLR (provided) on all unused circuits.
4
Polarity is shown on indicating circuits in an activated
(off-normal) condition.
5. Polarity reverses when output is activated.
6. Maximum current per output is 3 Amp. Maximum voltage
is 33VDC.
7. Outputs identified as Release are Special Application. All
other outputs are Regulated 24 VDC, Rated 3 Amp each, 3
Amp total for all 4 circuits.
8. All initiating and NAC/Release circuits are supervised and
power limited. See Main Board Wiring Specifications for
wire routing instructions. All frequencies are continuous.
9. Refer to Appendix A for test and maintenance information
VFR-500 PROGRAM TEMPLATES • 5403799 • REV A • 9/23
Fuse
4A-250VAC
P-Comm
Time Lag
+
-
A
N
L
PLINK
NON-POWER
SUPERVISED
PANEL OUTPUTS (INDICATING CIRCUITS)
RELEASE
GENERAL
SUPV
NON-POWER
ALARM
BELL
CIRCUIT
LIMITED AND
BELL
SUPERVISED
OUTPUT
OUTPUT
OUTPUT
3
BATT
1
2
RED +
POS
NEG
5.1K
5.1K
EOL
EOLR
EOLR
DIODE
12V BATT.
ASSY
OBSERVE POLARITY
WHEN CONNECTING
SMOKE DETECTORS
5.1K
5.1K
5.1K
EOLR
EOLR
EOLR
LOW AIR
PS40
EOLR
VALVE
TAMPER
OSYSU
PVCS
B
S
+
-
AUX OUT
ZONE 3
ZONE 4
ZONE 1
ZONE 2
SUP
SUP
HEAT OR
HEAT OR
VALV
LOW AIR
SMOKE
SMOKE
TAMP
SUP
DETECTORS
DETECTORS
SUP
PS40
PANEL INPUTS (INITIATING ZONES)
CONNECT TO NORMALLY OPEN DEVICES
OR COMPATIBLE 2 WIRE SMOKE
DETECTORS.
MAXIMUM LINE RESISTANCE: 100 OHMS
(EXCEPT WITH LINEAR HEAT DETECTION)
OPTIONAL CA2Z MOUNTING LOCATION
ZONE 5 AND 6 ONLY
RELEASE
RELAY CONTACTS
CIRCUIT
DRY CONTACTS RATED AT 3A, 30VDC
OUTPUT
TROUBLE
ALARM
4
COM
NO
NC
COM
NO
TROUBLE CONDITION
ALARM CONDITION
SMOKE DET.
PANEL PROBLEM
HEAT DET.
LOSS OF AC
PULL STATION
LOSS OF BATTERY
WIRING PROBLEM
WATERFLOW
EOL
DIODE
ASSY
10. Maximum resistance on outputs is 10 ohms. Maximum
resistance on outputs programmed as releasing, is 1
divided by current requirements of solenoid.
See Appendix C for smoke detector compatibility data.
See Battery Calculation Worksheet for battery information.
56
5.1K
5.1K
EOLR
EOLR
PS10
PS40
5.1K
EOLR
ZONE 5
ZONE 6
ZONE 7
LOW AIR
SUP
MANUAL
ALARM
RELEASE
OPTIONAL
CA2Z CLASS
A MOULE
EACH CA2Z WILL
CONVERT 2 CLASS B
ZONES INTO 2
CLASS A ZONES
OPTIONAL CLASS A
CONNECTIONS
EOLR IS NOT USED
FOR CLASS A
WTRFL
SUPV
RELEASE
NC
COM
NO
NC
COM
NO
NC
DWG #3550-3
WATERFLOW
RELEASE
SUPERVISORY
LOW AIR
VALVE TAMPER
Legend
Initiating device
Notification appliance
eAEROSOL
eA
z
eMatch Protection assy.
End-of-Line diode assy.

Advertisement

loading