1. DESCRIPTION
The Viking Model B-1 Par-3 Release Control Panel is a supervised, 24 Volt, microprocessor-
controlled Release Control Panel. The panel is designed to operate up to two electric release
devices (usually solenoid valves) in the release piping of deluge or preaction systems. The
panel is available for use with either 120 VAC or 230 VAC power supplies. A built-in battery com-
partment holds two 12 Volt batteries that are charged by an internal battery charger. Batteries
are available to provide up to 90 hours of backup power during AC power failure.
The Model B-1 Release Control Panel can be used with a wide range of compatible initiating
devices, such as heat (including linear heat detection systems like the Protectowire Systems),
photoelectric, ionization, and smoke detectors.
A dip switch 'Function Selector' allows fi eld programming for one of four possible input/output
combinations (refer to Table 2).
In fi re conditions, when an initiating device circuit (or predetermined combination of circuits) is
energized, the panel activates a combination of release device circuits and alarm circuits ac-
cording to the 'Function Selector' setting. On the panel's display board, the appropriate Alarm,
Trouble, and Supervisory LED's will fl ash until the event has been acknowledged. After depress-
ing the Tone or Alarm Silence button, the LED will remain steadily illuminated until the panel is
reset.
2. LISTINGS AND APPROVALS
Refer to Table 1
3. TECHNICAL DATA
I. Specifications
A. Enclosure
Dimensions: 16.125" high x 14.625" wide x 5.375" deep (50 cm x 37,1 cm x 13,7 cm)
Weight: 23 lbs. (10,4 kg)
Finish: Red Enamel
Vented Enclosure
B. Environment
Temperature: 32 °F to 120 °F (0 °C to 48 °C)
Humidity: 85% Relative Humidity (non-condensing) at 90 °F (32 °C) maximum
C. AC Power
Par-3 and Par-3C: 120 VAC, 50/60 Hz, 1.2 amps
Par-3E: 230 VAC, 50 Hz, 0.65 amps
Wire size: minimum #14 AWG with 600 V insulation
D. Battery
Type- Lead Acid
Maximum charging circuit: 27.6V, 1.5 A See ACCESSORIES for batteries available from Viking.
E. Initiating Device (Input) Circuits
Four style B (Class B)/Style D (Class A) circuits
Input 1: Detection Circuit
Input 2: Detection Circuit
Input 3: Waterfl ow (Alarm Pressure Switch)
Input 4: Supervisory Circuit
F. System Alarm
Power limited circuitry
Fuses: 2AG, 4 amperes
Normal operating voltage: 24VDC (ripple = 10mV peak to peak)
Alarm Current: 15mA minimum
Short circuit current: 40mA maximum
Maximum detector current in standby: 2 milliamps (peak) per zone
Maximum loop resistance: 100 ohms
End-of-Line resistor: 4.7K (provided)
Form No. F_063092
TECHNICAL DATA
Revised page replaces page 270 a-g dated August 17, 2006
Deluge Devices 270a
RELEASE CONTROL PANEL
MODEL B-1
Viking Technical Data may be found on
The Viking Corporation's Web site at
http://www.vikinggroupinc.com.
The Web site may include a more recent
edition of this Technical Data Page.
(Added California State Fire Marshal approval)

Advertisement

Table of Contents
loading

Summary of Contents for Viking B-1

  • Page 1 90 hours of backup power during AC power failure. The Model B-1 Release Control Panel can be used with a wide range of compatible initiating devices, such as heat (including linear heat detection systems like the Protectowire Systems), photoelectric, ionization, and smoke detectors.
  • Page 2 L. Zone Relay Module • Model B-1 Panels include one Zone Relay Module (4XZM) providing dry Form-C contacts controlled by each of the four output circuits plus one general alarm and one panel/fi eld-wiring trouble relay. See Table 2. M. Power Outputs •...
  • Page 3 2. Zone Relay Module (4XZM) (Viking Part No. 07912) • Model B-1 Panels can accommodate a second 4XZM Zone Relay Module (one included in each panel) or one of the following two Modules: 3. Transmitter Module (4XTM) (Viking P/N 07909) •...
  • Page 4: Installation

    Prior to energizing the panel: Verify that dip switches controlling panel operation are in the proper position for the system used. Refer to Table 2 and VIKING FIELD WIRING DIAGRAMS. Verify that all modules are securely and properly positioned on their pins. If a module is loose, carefully align all pins and press firmly into position.
  • Page 5 Place batteries inside the battery compartment of the Par-3 Release Control Panel with the unused terminals toward the open door. Install batteries in the upright position only. Plug the plug-in connector to J9 on the main board of the panel. (Refer to Figure 2 and VIKING FIELD WIRING DIAGRAMS.) DO NOT install jumper at this time.
  • Page 6 AGED BY REMOVING AND/OR INSERTING CARDS, MODULES, OR INTERCONNECTING CABLES WHILE THE PANEL IS ENER- GIZED. 7. AVAILABILITY The Viking Model B-1 Release Control Panel is available through a network of domestic and international distributors. See the Viking Corp. Web site for closest distributor or contact The Viking Corporation. 8. GUARANTEES For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
  • Page 7: Mode Description

    RELEASE CONTROL PANEL TECHNICAL DATA MODEL B-1 The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058 Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com Table 2 - Dip Switch Settings for System Configuration Modes DIP SWITCH SETTINGS...
  • Page 8 Deluge Devices 270h January 12, 2007 RELEASE CONTROL PANEL TECHNICAL DATA MODEL B-1 The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058 Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com Figure 2 - Replacement Parts PART ITEM NO.