Wiring Diagram Program #23
Single Hazard, 4 Detection Zones Mapped to 1 Release
Circuit, 1 Supervisory Zone, 1 Abort Circuit
FROM DEDICATED UNSWITCHED
CIRCUIT IN SERVICE PANEL
120VAC-240VAC 50/60 HZ
USE 14AWG OR HEAVIER GAUGE
WIRE WITH 600V INSULATION
LINE
NEUTRAL
EARTH GROUND
AC IN CONNECTOR
NON-POWER
LIMITED AND
SUPERVISED
BATTERY CABLE
OBSERVE POLARITY
RED +
BLACK -
POS
NEG
NOTES:
12V BATT.
1. Connect only UL Listed 24VDC devices to indicating
circuits.
2. Connect EOL Diode assembly IN SERIES with solenoid
on release circuit
3. Install EOLR (provided) on all unused circuits.
4
Polarity is shown on indicating circuits in an activated
(off-normal) condition.
5. Polarity reverses when output is activated.
6. Maximum current per output is 3 Amp. Maximum voltage
is 33VDC.
7. Outputs identified as Release are Special Application. All
other outputs are Regulated 24 VDC, Rated 3 Amp each, 3
Amp total for all 4 circuits.
8. All initiating and NAC/Release circuits are supervised and
power limited. See Main Board Wiring Specifications for
wire routing instructions. All frequencies are continuous.
9. Refer to Appendix A for test and maintenance information
VFR-500 PROGRAM TEMPLATES • 5403799 • REV A • 9/23
Fuse
4A-250VAC
P-Comm
Time Lag
L
N
+
-
A
B
PLINK
PANEL OUTPUTS (INDICATING CIRCUITS)
GENERAL
TROUBLE
SPRVSRY
NON-POWER
ALARM
LIMITED AND
OUTPUT
OUTPUT
SUPERVISED
OUTPUT
2
3
1
BATT
POS
NEG
5.1K
5.1K
5.1K
EOLR
EOLR
EOLR
12V BATT.
OBSERVE POLARITY
WHEN CONNECTING
SMOKE DETECTORS
5.1K
5.1K
EOLR
EOLR
EOLR
5.1K
S
+
-
AUX OUT
ZONE 1
ZONE 2
ZONE 3
ABORT
SUP
HEAT OR
HEAT OR
SMOKE
DETECTORS
DETECTORS
PANEL INPUTS (INITIATING ZONES)
CONNECT TO NORMALLY OPEN DEVICES
OR COMPATIBLE 2 WIRE SMOKE
DETECTORS.
MAXIMUM LINE RESISTANCE: 100 OHMS
(EXCEPT WITH LINEAR HEAT DETECTION)
OPTIONAL CA2Z MOUNTING LOCATION
RELEASE
RELAY CONTACTS
CIRCUIT
DRY CONTACTS RATED AT 3A, 30VDC
OUTPUT
TROUBLE
ALARM
4
COM
NO
NC
COM
TROUBLE CONDITION
ALARM CONDITION
PANEL PROBLEM
SMOKE DET.
HEAT DET.
LOSS OF AC
PULL STATION
LOSS OF BATTERY
WATERFLOW
WIRING PROBLEM
EOL
DIODE
ASSY
10. Maximum resistance on outputs is 10 ohms. Maximum
resistance on outputs programmed as releasing, is 1
divided by current requirements of solenoid.
See Appendix C for smoke detector compatibility data.
See Battery Calculation Worksheet for battery information.
52
5.1K
5.1K
5.1K
EOLR
EOLR
ZONE 4
ZONE 5
ZONE 6
ZONE 7
HEAT OR
HEAT OR
SMOKE
SMOKE
SMOKE
DETECTORS
DETECTORS
WTRFL
SUPV
RELEASE
NO
NC
COM
NO
NC
COM
NO
NC
SUPERVISORY
LOW AIR
VALVE TAMPER
DWG #3550-14a
WATERFLOW
RELEASE
Legend
Initiating device
Notification appliance
Solenoid
S
End-of-Line diode assy