Download Print this page

Viking VFR-500 Manual page 62

Conventional releasing panel
Hide thumbs Also See for VFR-500:

Advertisement

Wiring Diagram Program #33
Redundant Solenoids Single Interlock with Single Zone Activation
FROM DEDICATED UNSWITCHED
CIRCUIT IN SERVICE PANEL
120VAC-240VAC 50/60 HZ
USE 14AWG OR HEAVIER GAUGE
WIRE WITH 600V INSULATION
LINE
NEUTRAL
EARTH GROUND
AC IN CONNECTOR
BATTERY CABLE
OBSERVE POLARITY
POS
NEG
12V BATT.
NOTES:
1. Connect only UL Listed 24VDC devices to indicating
circuits.
2. Connect EOL Diode assembly IN SERIES with solenoid
on release circuit
3. Install EOLR (provided) on all unused circuits.
4
Polarity is shown on indicating circuits in an activated
(off-normal) condition.
5. Polarity reverses when output is activated.
6. Maximum current per output is 3 Amp. Maximum voltage
is 33VDC.
7. Outputs identified as Release are Special Application. All
other outputs are Regulated 24 VDC, Rated 3 Amp each, 3
Amp total for all 4 circuits.
8. All initiating and NAC/Release circuits are supervised and
power limited. See Main Board Wiring Specifications for
wire routing instructions. All frequencies are continuous.
9. Refer to Appendix A for test and maintenance information
VFR-500 PROGRAM TEMPLATES • 5403799 • REV A • 9/23
Fuse
4A-250VAC
P-Comm
Time Lag
+
-
N
L
PLINK
NON-POWER
LIMITED AND
SUPERVISED
PANEL OUTPUTS (INDICATING CIRCUITS)
RELEASE
GENERAL
WATERFLOW
NON-POWER
ALARM
w/ ALARM
CIRCUIT
LIMITED AND
SUPERVISED
OUTPUT
OUTPUT
OUTPUT
BATT
1
2
RED +
BLACK -
POS
NEG
5.1K
5.1K
EOLR
EOLR
12V BATT.
DIODE
ASSY
OBSERVE POLARITY
WHEN CONNECTING
SMOKE DETECTORS
5.1K
5.1K
EOLR
EOLR
LOW AIR
PS40
EOLR
VALVE
TAMPER
OSYSU
PVCS
A
B
S
+
-
AUX OUT
ZONE 1
ZONE 2
ZONE 3
SUP
SUP
HEAT OR
VALV
LOW AIR
SMOKE
TAMP
SUP
DETECTORS
SUP
PS40
PANEL INPUTS (INITIATING ZONES)
CONNECT TO NORMALLY OPEN DEVICES
OR COMPATIBLE 2 WIRE SMOKE
DETECTORS.
MAXIMUM LINE RESISTANCE: 100 OHMS
(EXCEPT WITH LINEAR HEAT DETECTION)
OPTIONAL CA2Z MOUNTING LOCATION
RELEASE
CIRCUIT
DRY CONTACTS RATED AT 3A, 30VDC
OUTPUT
TROUBLE
4
3
COM
NO
NC
COM
ALARM CONDITION
TROUBLE CONDITION
PANEL PROBLEM
SMOKE DET.
HEAT DET.
LOSS OF AC
LOSS OF BATTERY
PULL STATION
WATERFLOW
WIRING PROBLEM
EOL
EOL
DIODE
ASSY
10. Maximum resistance on outputs is 10 ohms. Maximum
resistance on outputs programmed as releasing, is 1
divided by current requirements of solenoid.
See Appendix C for smoke detector compatibility data.
See Battery Calculation Worksheet for battery information.
62
5.1K
5.1K
5.1K
EOLR
EOLR
EOLR
PS10
5.1K
EOLR
ZONE 4
ZONE 5
ZONE 6
ZONE 7
HEAT OR
SUP
SUP
MANUAL
SMOKE
RELEASE
DETECTORS
RELAY CONTACTS
WTRFL
ALARM
SUPV
RELEASE
NO
NC
COM
NO
NC
COM
NO
NC
SUPERVISORY
LOW AIR
VALVE TAMPER
OPTIONAL
CA2Z CLASS
A MOULE
EACH CA2Z WILL
CONVERT 2 CLASS B
ZONES INTO 2
CLASS A ZONES
OPTIONAL CLASS A
CONNECTIONS
EOLR IS NOT USED
FOR CLASS A
DWG #3550-3
WATERFLOW
RELEASE
Legend
Initiating device
Notification appliance
eAEROSOL
eA
z
eMatch Protection assy.
End-of-Line diode assy.

Advertisement

loading