Viking VFR-500 Manual page 53

Conventional releasing panel
Hide thumbs Also See for VFR-500:

Advertisement

Program #23 Mode
1. Apply power to panel.
2. Press ENT to enter PROGRAM mode
3. Press 6 or scroll down to #6 and press ENT, (The selection is indicated by a flashing arrow next to the number.
4. Enter the password. (Factory default is 1111)
5. Press 1 or press ENT. (1 should be the highlighted selection)
6. The display shows the current program number. Press 23 to change to program 23. Press ENT.
7. Press 1 to accept the change.
8. Press ENT to accept the change.
Single Hazard, 4
Dectection Zones Mapped
to 1 Release Circuit 1
Supervisory Circuit, 1
Abort Circuit
OUTPUTS
#1 ALARM INDICATING
#2 TROUBLE
#3 SUPERVISORY
#4 RELEASE
Description:
Single Hazard, 4 detection zones mapped to 1 release
Inputs:
1 supervisory zone, 4 detection zones, 1 abort circuit
Outputs:
1 general alarm, 1 trouble, 1 supervisory, 1 release circuit
Operation:
Activation of any detection zone will activate the alarm output #1 and start the pre-discharge timer for the
release circuit output #4.
Activation of the supervisory zone will operate the supervisory bell.
A trouble condition (low battery, wire problem, etc.) will operate the trouble bell.
When either zone 3, 4, 5, or 6 is in alarm, outputs 1 & 4 will operate
When the zone 6 supervisory zone is activated - output #3 (supervisory bell) will operate.
When the panel is in a trouble condition - output #2 (trouble bell) will operate.
VFR-500 PROGRAM TEMPLATES • 5403799 • REV A • 9/23
#1
#2
Abort
Supervisory
X
PROGRAM #23
CONVENTIONAL INPUT ZONES
#3
#4
Detection
Detection
X
X
X
X
53
#5
#6
Detection
Detection
X
X
X
X
#7
Unused