AcuLink 810 Data Aquisition Server

9.6 SNMP

The AcuLink 810 supports the Simple Network Management Protocol (SNMP) which allows
for reporting the 810 device data to the management station. The SNMP settings can be
found on the SNMP page under the Protocols tab.
SNMP Enable: Select Enable for the SNMP protocol
SNMP Version: Users can select either SNMPv2c or SNMPv3.
Version 2: requires a read only community string to be configured.
Version 3: requires authentication and privacy protocol.
Port: The default SNMP port is 161, the range is 16100-16199
The AcuLink also supports SNMP trap notifications, where the user can receive a trap notifi-
cation for any alarms that are triggered for devices on the AcuLink.
Trap Enable: Select enable for trap notifications
Trap Target 1-4: Users can configure up to 4 trap targets, where the trap targets must be an
IP address.
Buffer Size: Enter the size of the buffer for the amount of notifications will be stored before
being sent to the management station. A maximum of 30 notifications can be stored.
Report Hold Time: Enter the time in seconds for how long the notification will be in queued
before it gets sent to the management station. By default, this setting is configured to 0 so
the notification will be sent immediately after an event occurs. This setting could be config-
ured from 0-30 seconds.